Troubleshooting by Indication on the Remote Controller
108
Troubleshooting
Does low
or high
pressure vary even
instantaneously when
restarting
compressor?
Are
inverter output
voltages the same for
3 phases?
Check
and see
whether
compressor is short-
circuited or
ground.
Is high
differential pressure
starting?
Is
the UVWN
wiring normal?
Is
the stop valve
open?
NO
YES
YES
NO
Open the stop
valve.
NO
YES
YES
NO
NO
Connect
correctly.
YES
Remedy the
cause.
YES
Replace the
compressor.
NO
Replace the
outdoor unit
inverter PCB.
Replace the
compressor.
Check the installation
conditions.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.