Troubleshooting by Indication on the Remote Controller
137
Troubleshooting
NO
YES
YES
Replace the
discharge pipe
thermistor.
NO
Replace the
outdoor unit main
PCB.
Check
if discharge
pipe thermistor
property is normal.
(
∗
1)
Check if
temperature of
discharge pipe by
using service checker
is the same with actual
measurement value
of discharge pipe
thermistor.
Service Checker
Connect the service checker to compare the
temperature of discharge pipe by using service
checker with actual measurement value of
discharge pipe thermistor
CHECK 11
.
· Discharge pipe thermistor is normal and the
temperature detection of the main PCB is also
normal.
· Actually the temperature of discharge pipe is high.
CHECK 3
Remove the factor of overheat
operation.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
Connect the service
checker.
Press reset and start
operation again.
Содержание VRVII