Troubleshooting by Indication on the Remote Controller
230
Troubleshooting
NO
YES
NO
Connect
transmission
wiring and turn
ON again.
Are the
connectors
between the main
PCB, and inverter
PCB connected
securely?
YES
NO
Defective
outdoor (outside)
unit main PCB or
defective inverter
PCB.
The micro-
computer monitor
(green) on the
inverter PCB is
blinking.
YES
Replace the
inverter PCB.
When the LC
error occur
again, replace
the control PCB.
The
voltage
between 2 pins
of connector on the
inverter unit is 220 ~
240 V.
The
transmission
wiring between the
outdoor (outside) unit
PCB inverter unit is
disconnected.
YES
Fix the
disconnection
and turn ON
again.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
NO
Check the noise
filter for
disconnection,
and check the
power supply
wiring of the
inverter PCB.
Содержание VRVII