Troubleshooting by Indication on the Remote Controller
47
Troubleshooting
YES
NO
External
protection
device is connected
to terminals T1 and
T2 of the indoor
unit terminal
block.
ON/OFF
input from
outside (mode
No. 12, first code
No. 1) has been set
to external protection
device input (second
code No. 03) by
remote
controller.
YES
NO
Actuation of
external
protection
device.
Check the setting state of
the external ON/OFF
input by remote
controller.
Change the
second code No.
to "01" or "02".
Replace the
indoor unit PCB.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.