Troubleshooting by Indication on the Remote Controller
239
3.56
P4
Inverter Radiation Fin
Thermistor Abnormality
Remote Controller Display
P4
Applicable Models
VRVIII, III-S and III-Q Series
Method of Error Detection
Resistance of radiation fin thermistor is detected when
the compressor is not operating.
Error Decision Conditions
When the resistance value of thermistor becomes a value
equivalent to open circuited or short circuited status
∗
Error is not decided while the unit operation is
continued.
"
P4
" will be displayed by pressing the INSPECTION
button.
Supposed Causes
Defective radiation fin thermistor
Defective inverter PCB
Defective inverter compressor
Defective fan motor