Troubleshooting by Indication on the Remote Controller
325
Remote Controller Display
UA
Applicable Models
All indoor models
VRVIII-S Series
Method of Error Detection
A difference occurs in data by the type of refrigerant
between indoor and outdoor units.
The number of indoor units is out of the allowable range.
Incorrect signals are transmitted among the indoor unit,
BS unit, and outdoor unit.
Error Decision Conditions
The error decision is made as soon as either of the
abnormalities aforementioned is detected.
Supposed Causes
Excess of connected indoor units
Defective outdoor unit PCB
Mismatching of the refrigerant type of indoor and
outdoor unit.
Setting of outdoor unit PCB was not conducted after
replacing to spare PCB.
The outdoor unit PCB was replaced with wrong one.