Troubleshooting by Indication on the Remote Controller
340
Refer to P.373.
Disconnect the
transmission wiring of the
master unit centralized
control equipment, and
then check the voltage
between the transmission
terminals (F1 and F2) of
the master unit
transmission equipment
using a multiple meter.
D
Is the
voltage
between the
terminals F1 (+) and F2
(-) in the range of
15.2 to 17.6
VDC?
NO
Replace the
centralized
control
equipment.
Has
the master
unit central setting
connector been
connected?
NO
YES
Correct the
connection of the
connector.
YES
Centralized
control
equipment:
Normal
It is supposed
that the error
results from
external factors
(e.g. noises) from
other equipment.
CHECK 13