Troubleshooting by Indication on the Remote Controller
291
Are
the indoor-
outdoor, outdoor-
outdoor connecting
wires normal?
NO
Correct the
connecting wires.
Lights
do not go out for
12 minutes or
more.
YES
NO
Press the
RESET button on
the main PCB of
the outdoor unit
main PCB. Keep
pressing for 5
seconds or more.
Reset the power supply.
A
Correct the
voltage (400V).
Replace the
outdoor unit
PCB.
NO
NO
YES
Does
the normal
condition monitor
for the micro-computer
(HAP) on the outdoor
unit PCB blink?
Is the
voltage between
R, S terminals on the
outdoor unit PCB
400V?
YES
Does
the LED in
preparation mode
(H2P) on the outdoor
unit PCB
blink?
NO
YES
YES
Replace the fuse.
YES
Is the fuse on
the outdoor unit PCB
blown?
NO
B