Troubleshooting by Indication on the Remote Controller
183
Troubleshooting
Are the
characteristics
of the high
pressure sensor
normal? (Make a
comparison between the
voltage
characteristics (
∗
1)
and the gauge
pressure.)
NO
YES
YES
Replace the high
pressure sensor.
Is
the
PCB
pressure
detection normal?
(Make a comparison
between the checker
pressure data and
the voltage
characteristics
(
∗
1).)
NO
Replace the
outdoor unit main
PCB.
Confirm which high
pressure sensor is
abnormal using outdoor
unit "monitor mode".
1.Set the high pressure
gauge upright.
2.Connect the checker
for VRV to the gauge.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
A