Troubleshooting by Indication on the Remote Controller
218
Higher voltage than actual is displayed when the inverter
output voltage is checked by tester.
A
YES
After
turning ON
again, "
L8
" blinks
again.
NO
Reset and
restart.
Compressor
inspection
Inspect
according to the
diagnosis
procedure for
odd noises,
vibration and
operating status
of the
compressor.
YES
NO
Replace the
inverter PCB.
Inverter
output
voltage check
Inverter output
voltage is not
balanced. (Normal if
within ±10V for Y1, YL
power supply and ±5V
for TL power supply)
Must be measured
when frequency
is stable.