3
|
Troubleshooting
Service manual
66
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
2
Check if the power supply is compliant with the regulations. See
254].
Possible cause:
▪
Faulty or disturbance of the power supply (power supply MUST be within
range of nominal operating voltage ±4%),
▪
Power drop,
▪
Short circuit.
3
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
4
Check that all stop valves of the refrigerant circuit are open. See
256].
Possible cause:
Closed stop valve in the refrigerant circuit.
5
Check if the refrigerant circuit is clogged. See
256].
Possible cause:
Clogged refrigerant circuit.
6
Check if the refrigerant circuit is correctly charged. See
256].
Possible cause:
Refrigerant overcharge or shortage.
7
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.3.69 LC-00 – Malfunction in communication system of outdoor unit
Trigger
Effect
Reset
Malfunction in
communication system
inside the unit.
Unit will stop operating.
Manual reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
2
Perform a check of the outdoor unit fan motor. See
Possible cause:
Faulty outdoor unit fan motor.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
draft – 31/05/2022 15:53