4
|
Components
Service manual
207
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
a
b
a
Wiring
b
Ground wire
4
Loosen and remove the screw to disconnect the ground wire from the switch
box.
5
Remove the drip proof cover from the switch box.
a
b c
c
d
e
f
g
a
Drip proof cover
b
Cable clamp expansion valve harness
c
Cable clamp thermistor harness
d
Cable clamp 4‑way valve harness
e
Fan motor assembly harness
f
Main PCB
g
Compressor harness connector
6
Remove the cable clamps / tie straps from the expansion valve harness, the
two thermistor harnesses and the 4‑way valve harness.
7
Detach the fan motor assembly harness from the switch box.
8
Disconnect the connectors from the main PCB.
9
Disconnect the compressor harness connector.
10
Remove the switch box from the unit.
11
To install the switch box, see