EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
3
Open the drain valve to drain water from the water circuit. Collect the drained
water in a drain pan, bottle,….
a
A
B
a
a
A
Unit with built‑in backup heater
B
Unit without backup heater
a
Drain valve
4
To add water to the water circuit, see
269].
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To add water to the water circuit
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
202].
1
To fill the water circuit, use a field supply filling kit. Make sure you comply with
the applicable legislation.
2
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To open the stop valves of the water circuit
1
The stop valves are located outside the unit. Open the valves by placing them
in line with the piping.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To open the air purge valves of the water circuit
Prerequisite:
Stop the unit operation via the user interface.