5
|
Third party components
Service manual
274
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
Is the problem solved?
Action
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
5.5 External factors
5.5.1 Checking procedures
To check the outdoor temperature
1
The temperature ranges for the different operation modes of the unit can be
found in the databook on Business Portal.
INFORMATION
If the outdoor temperature is outside the range of operation, the unit may NOT
operate or may NOT deliver the required capacity.
Is the outdoor temperature within the
operating range?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Wait for the outdoor temperature to
return within the operating range.
To check the required space around the outdoor unit heat exchanger
1
Check if the space around the outdoor unit heat exchanger is sufficient. See
the installation manual for the required space specifications. Adjust as
needed.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.