4
|
Components
Service manual
216
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
7
Install a plug or cap on the refrigerant piping to avoid dirt or impurities from
entering the piping.
8
To install the refrigerant pressure sensor, see
To install the refrigerant pressure sensor
1
Remove the plug or cap from the refrigerant piping and make sure it is clean.
2
Install the refrigerant pressure sensor in the correct location.
3
Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02 MPa.
4
Wrap a wet rag around the refrigerant pressure sensor and any other
components near the pressure sensor and solder the refrigerant pressure
sensor pipe to the refrigerant pipe.
b
a
a
Refrigerant pressure sensor
b
Refrigerant pressure sensor pipe
CAUTION
Overheating the pressure sensor will damage or destroy it.
5
After soldering is done, stop the nitrogen supply after the component has
cooled‑down.
6
Connect the refrigerant pressure sensor connector to the connector X6Y.
7
Fix the refrigerant pressure sensor harness using new tie straps.
8
9
Add
refrigerant
to
the
refrigerant
circuit,
see
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
draft – 31/05/2022 15:53