3
|
Troubleshooting
Service manual
95
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
Possible failure
Root cause
Check
Repair
Too high (space heating) or
too low (space cooling)
setpoint on room
thermostat.
User set too high (space
heating) or too low (space
cooling) room setpoint by
schedule or manual
operation.
Check room thermostat
setpoint.
Adapt room thermostat
setpoint.
Root cause category: parameter (setting)
Possible failure
Root cause
Check
Repair
Too high leaving water
temperature (LWT) -
weather dependent.
Incorrect weather
dependent setting --> too
high LWT limit set
[1‑00]~[1‑09].
Check leaving water
temperature (LWT) high
limit in weather dependent
(setting [1‑03]).
Adapt high leaving water
temperature (LWT) limit
for weather dependent
heating (setting [1‑03]).
User interface thermostat
used with setting [C‑07] on
value 1 (= external
thermostat control).
Wrong setting of [C‑07] -
unit control method.
Check setting [C‑07].
Adjust setting to match
application - see installer
reference guide.
Pump keeps running all the
time during space heating
(cooling) operation.
Wrong setting of [F‑0D] -
pump operation.
Check pump operation
mode setting [F‑0D].
Change setting [F‑0D] from
continuous operation
(value 0) to Sample (1) or
Request (2). See installer
reference guide for
applicable value.
Setting disinfection
operation day [2‑00] was
set to 0 (each day).
Setting disinfection
operation day [2‑00] was
set to 0 (each day).
Check setting [2‑00].
Adjust setting if necessary.
Unit is running in
emergency operation and
is using backup heater
ONLY. [4‑06] is set to 1.
Unit is running in
emergency operation and
is using backup heater
ONLY. [4‑06] is set to 1.
Check setting [4‑06].
Adjust setting if necessary.
Backup heater equilibrium
point was set too high.
Setting "equilibrium
temperature" [5‑01] was
set too high.
Check setting [5‑01].
Change setting [5‑01] to
less quickly allow backup
heater operation.
Setting domestic hot water
operation mode [6‑0D]
NOT set optimally.
Setting domestic hot water
operation mode [6‑0D] is
set to 0 (reheat ONLY). This
will cause the system to
work too frequently in
domestic hot water
operation and less in space
heating.
Check setting [6‑0D] in
combination with the re-
heat setpoint [6‑0C].
It is advisable to set to
factory setting (
schedule) and program the
schedule to heat the
domestic hot water during
periods of no space
heating required.
draft – 31/05/2022 15:53