4
|
Components
Service manual
246
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
1
Insert a flat screwdriver in the slot of the rotor shaft of the water pump
(through the hole in the pump motor cover); press and turn the screwdriver to
rotate the water pump motor.
a
b
c
a
Hole
b
Water pump motor cover
c
Water pump motor
Does the rotor of the water pump
motor rotate smoothly?
Action
Yes
Perform an electrical check of the water
pump, see
No
Continue with the next step.
2
248].
3
Check for impurities or any objects that may block the water pump.
Any impurities or objects found?
Action
Yes
Remove the impurities or objects that
may block the water pump, see
No
Replace the water pump, see
To perform an electrical check of the water pump
1
First perform a mechanical check of the water pump, see
2
Turn ON the power of the unit.
3
Activate
Installer
on the user interface. See the installer reference guide
for the correct procedure.
4
Go to
Actuator test run
via the user interface.
5
Activate the
Pump
.
CAUTION
When the water pump is active and the connector PWM is disconnected from the
PCB, the water pump motor will run at full speed.
6
Check if the pump is working (by listening or by touching the pump).