4
|
Components
Service manual
106
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
NOTICE
Check the condition of the O-rings and replace if needed. Apply water or silicon
grease to the O-rings before installation.
7
Install the 3‑way valve body on the water piping.
8
If applicable, install the insulation around the 3‑way valve body.
9
Route the 3‑way valve motor harness through the grommet in the switch box.
10
Connect the 3‑way valve motor wiring to the wire terminal X2M.
11
Install new tie straps to fix the 3‑way valve harness.
12
Open the stop valves and add water to the water circuit if needed.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To install the 3-way valve motor
CAUTION
Make sure the 3‑way valve body axle is aligned with the 3‑way valve motor when
installing the 3‑way valve motor on the 3‑way valve body.The 3‑way valve motor is
shipped with the 3‑way valve knob in the central position. Do NOT change this
position!
1
The 3-way valve can be installed in accordance with one of the following four
configurations.
1
2
3
1
3
2
1
2
3
1
3
2
E3
E1
E2
E4
1
Water inlet
2
Domestic hot water exit
3
Space heating exit
2
Depending on the configuration used in your unit, put the 3‑way valve body
axle (notch) in the correct position (see image below).
draft – 31/05/2022 15:53
Содержание EBLA04E V Series
Страница 322: ...14 14...
Страница 323: ......
Страница 324: ...draft 31 05 2022 15 53 ESIE22 09 2022 05 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...