To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Possible cause:
Water flow is too low.
2
Check the minimum required water volume for your unit. See installer
reference guide.
Possible cause:
Water volume is too low.
3
Perform a check of the refrigerant pressure sensor. See
212].
Possible cause:
Faulty refrigerant pressure sensor.
4
Perform a check of the outlet water after heat exchanger thermistor. See
Possible cause:
Faulty outlet water after heat exchanger thermistor.
5
Check if the refrigerant circuit is correctly charged. See
256].
Possible cause:
Refrigerant overcharge or shortage.
6
Check if the refrigerant circuit is clogged. See
256].
Possible cause:
Clogged refrigerant circuit.
7
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
8
Perform a check of the hydro PCB. See
Possible cause:
Faulty hydro PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.3.15 89-06 – Heat exchanger freeze-up protection activated during cooling (warning)
Trigger
Effect
Reset
Water heat exchange
freezing abnormality
during cooling.
Outlet water temperature
<5°C or 1.5°C (glycol) for
5 seconds OR saturated
evaporation temperature
(pressure sensor) <−11°C
for 5 minutes from start
of cooling.
At second occurrence,
error 89‑05 is triggered.
Unit will stop operating.
Auto reset.