4
|
Components
Service manual
212
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
a
d
d
e
e
d
d
e
e
c
b
d
e
d
e
a
L803
b
L804
c
L903
d
Measuring point
e
Measuring point
Is the inductance measurement
correct?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next step.
No
Replace the reactor, see
4.17.2 Repair procedures
As the reactors are part of the main PCB, replace the complete main PCB. See
184].
4.18 Refrigerant pressure sensor
4.18.1 Checking procedures
To perform an electrical check of the refrigerant pressure sensor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
202].
1
Turn ON the power of the unit.
2
Connect a pressure gauge to the gas service port. Read the pressure.
3
Using the graphic below, determine the expected sensor output voltage based
on the pressure obtained in the previous step.
draft – 31/05/2022 15:53