4
|
Components
Service manual
182
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
LED
Description
Behaviour
LD2
Indication of TCP/IP
communication with the
router.
▪
LED
ON:
normal
communication.
▪
LED flashing: communication
problem.
Check
TCP/IP
communication
with
the
router.
LD3
Indication of communication
with the indoor unit.
▪
LED
ON:
normal
communication.
▪
LED flashing: communication
problem.
Check
the
communication between the
LAN adapter and the unit
PCB,
LD4
(a)
Indication of Smart Grid
activity.
▪
LED ON: system running in
the "Recommended ON",
"Forced ON", or "Forced OFF"
Smart Grid operation mode.
▪
LED OFF: system running in
the
"Normal
operation"
Smart Grid operation mode,
or
operating
in
normal
operation conditions (space
heating/cooling, production
of domestic hot water).
▪
LED flashing: LAN adapter
performing a Smart Grid
compatibility check.
(a) This LED is ONLY active for BRP069A61 (present for BRP069A62, but ALWAYS
inactive).
INFORMATION
▪
When the LAN adapter performs a Smart Grid compatibility check, LD4 flashes.
This is NOT erroneous behaviour. After a successful check, LD4 will either stay ON
or go OFF. When it keeps flashing for more than 30 minutes, the compatibility
check failed, and NO Smart Grid operation is possible.
a
b
c
d
a
LED 1: heartbeat
b
LED 2: LAN communication
c
LED 3: P1/P2 communication
d
LED 4: smart grid control active
draft – 31/05/2022 15:53
Содержание EBLA04E V Series
Страница 322: ...14 14...
Страница 323: ......
Страница 324: ...draft 31 05 2022 15 53 ESIE22 09 2022 05 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...