4
|
Components
Service manual
101
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
1
2
3
1
3
2
1
2
3
1
3
2
E3
E1
E2
E4
1
Water inlet
2
Domestic hot water exit
3
Space heating exit
5
De-activate
DHW operation
and activate
Space operation
via the user
interface.
6
Use a contact thermometer to measure the temperature at the 3‑way valve
water inlet, the domestic hot water exit and the space heating exit.
Exit
Temperature
Domestic hot water
"Much" lower than the 3-way valve inlet
Space heating
Same as the 3-way valve inlet
Both temperature checks performed
above are correct?
Action
Yes
Component is OK. Return to the
troubleshooting of the specific error
and continue with the next step.
No
Perform a position check of the 3-way
valve (manual procedure), see
To perform a position check of the 3-way valve (manual procedure)
Prerequisite:
First perform a position check (automatic procedure), see
99].
1
Manually put the 3‑way valve in the domestic hot water position by rotating
the 3‑way valve knob.
2
Use a contact thermometer to measure the temperature at the 3‑way valve
water inlet, the domestic hot water exit and the space heating exit.
Exit
Temperature
Domestic hot water
Same as the 3-way valve inlet
Space heating
"Much" lower than the 3-way valve inlet
draft – 31/05/2022 15:53