4
|
Components
Service manual
120
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
Are the measured voltages of the
backup heater contactor correct
(contacts closed)?
Action
No
Skip the next steps and continue with
the operating voltage check of the
contactor.
5
Deactivate backup heater: Step 1.
6
Measure the voltage between the following terminals of the backup heater
contactor.
▪
K1M: 1‑3
The measured voltages MUST be 0 V AC (contacts open).
Are the measured voltages of the
backup heater contactor correct
(contacts open)?
Action
Yes
heater and continue with the next
procedure.
No
Continue with the next step.
7
Measure the operating voltage on the contactor.
Result:
The measured operating voltage MUST be:
▪
230 V AC when the contacts should be closed.
▪
0 V AC when the contacts should be open.
Is the measured operating voltage of
the backup heater contactor correct?
Action
Yes
Replace the specific backup heater
contactor(s), see
No
Check for the reason of faulty operating
voltage (wiring, faulty contact, …), see
Problem solved?
After all checking procedures listed above have been performed:
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Repair procedures
To remove the backup heater
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
202].
1
Drain water from the water circuit, see
269].
2
Cut the tie strap(s) and remove the insulation from the backup heater.
draft – 31/05/2022 15:53