5
|
Third party components
Service manual
269
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
To check the main water supply and pressure
1
Check that the main water supply and pressure of the installation is within the
expected range (>1 bar).
Main water supply and pressure within
expected range?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Adjust the main water supply of the
installation, see
269].
5.3.2 Repair procedures
To remove the external pump from the water circuit
1
If an external pump is found in the installation outside the unit, the pump
MUST be programmed as such that it ONLY works when the water pump of
the unit is off. See the specific dealer manual of the external pump for this
procedure.
a
a
b
c
d
a
External pump
b
By‑pass
c
Underfloor heating circuit
e
Radiators circuit
2
If impossible to program as such, the external pump needs to be removed
from the installation.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To remove/drain water from the water circuit
INFORMATION
This procedure partially drains the water circuit, sufficient for component
replacement.
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Close the stop valves of the water circuit.
2
Open the air purge valves, see
269].
draft – 31/05/2022 15:53