1.7 Ai Unit (DAM101A51)
321
Adaptor
1.7.3 Installation
1.7.4 Wiring Work and Initial Setting
1. Wiring connection
294
(75)
The device with the lid open
(210.5)
154
Indentations
for screw holes
The lead line length for the
outside thermometer is
approximately 50cm from
the bottom of the device.
(356.5)
The installation orientation
for the device is set
ahead of time. Do not
install the device
upside down.
PC board ASSY
This device is mounted with 4 screws.
Open the four indentations for the screw holes with self tapping screws or drill
them and secure them with the 4 screws.
(The recommended screw size is M4. Screws should be procured locally.)
Above
Screws
First, remove the lid from the main unit. (5 screws) Do not lose the removed screws.
You will need them when you close the lid after all work is done.
There are 4 types of wiring for the device.
Indoor
unit
Use the included sensor
Indoor
unit
When extending the included harness --- max. 15m
1.25mm
2
Outdoor
unit
Multi-purpose sensor
Power wiring
X1M
L, N
DIII-A1
(DAM101A51)
Outdoor
unit
No polarity
Specifications for electric wiring used
Communication
wiring
Power supply voltage: max. 200 - 240V (50/60Hz)
Remarks
Indoor
unit
DIII-NET
Communication
External
Temperature
sensor
Name
Do not clamp
simultaneously
with powerful
wiring
External temperature
sensor
-
Earth leakage
breaker
~ AC 200 - 240V
(power consumption
max. 10W)
Indoor
unit
X2A
X1A
X2M
F1, F2
Multi-purpose
sensor
intelligent Manager III
(DAM602B51/52)
10A
The DIII-NET communication line connecting
the device should be no greater than 64Gr,
including the device.
(The DIII-NET communication addresses
which can be used are 1 - 0 to 4 - 15.)
DC 0 - 5V sensor can be connected
(procured locally)
System wiring
Sheathed vinyl cord or cable 0.75
~
1.25mm
2
(balanced-type) --- max. length 1000m
(up to total extension 2000m)
(Total extension length 1500m when using shield wire)
Содержание D-BACS
Страница 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Страница 17: ...xvi 1 5 Open Network Glossary Introduction ...
Страница 41: ...24 Outline of D BACS System ...
Страница 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Страница 88: ...3 6 Wired Remote Controller with Weekly Schedule Timer BRC1D61 71 Remote Controllers 3P107422 3D ...
Страница 102: ...5 2 Wireless Remote Controller BRC4C 7C 7E 85 Remote Controllers 5 2 Wireless Remote Controller BRC4C 7C 7E ...
Страница 103: ...86 5 3 Simplified Remote Controller BRC2C51 BRC2A51 Remote Controllers 5 3 Simplified Remote Controller BRC2C51 BRC2A51 ...
Страница 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Страница 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Страница 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Страница 215: ...198 3 8 Wiring Example intelligent Manager ...
Страница 235: ...218 Interface for Use in BACnet ...
Страница 249: ...232 7 1 Node Objects Interface for use in LONWORKS 7 Object Details 7 1 Node Objects 7 2 DIII NET Common Objects ...
Страница 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Страница 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Страница 285: ...268 1 6 Notes Power Proportional Distribution P P D ...
Страница 319: ...302 1 5 Dio Unit DEC102A51 Adaptor 1 5 2 Part Names and Functions 1 Appearance Dio Unit DEC102A51 ...
Страница 329: ...312 1 6 Di Unit DEC101A51 Adaptor 1 6 2 Part Names and Functions 1 Appearance Di Unit DEC101A51 ...