80
4.5 <KRCS01-1A> Remote Sensor
Remote Controllers
4.5
<KRCS01-1A> Remote Sensor
The built-in temperature control thermistor of the indoor unit is mounted in the intake port of the main body. Some
difference can occur between the temperature setting of the built-in thermistor and the actual indoor temperature. In such
case, remove the thermistor from the indoor unit and remount it near the living area so that the remote sensor can sense
the temperature of the living area.
This kit can be used for all indoor units in the Skyair series and the VRV series.
Examples:
Skyair: FHYC
VRV: FXYC
If you are unsure if this kit can be used with your particular indoor unit, check the type of thermistor (inlet air temperature
sensor).
The type of thermistor is ST8601.
It is shaped as shown below.
<1> Kit components
This kit includes the following components.
<2> Mounting
i) Selecting the mounting position
The remote sensor incorporates a thermistor to sense the temperature.
Select mounting position carefully on the basis of the following considerations.
A location with an average temperature for the room being air conditioned
Out of direct sunlight
Away from the influence of other heat sources
Not directly exposed to the outlet air from the air conditioner
Not directly exposed to the air entering the room when a door is opened.
ii) Mounting
Surface mounting
z
Break out the wiring hole tabs in the sensor box using nippers or a similar tool.
z
Screw the sensor box securely to the wall surface. (2 points)
z
Wire to the electronic control unit in the indoor unit by first removing the existing thermistor (inlet air temperature
sensor) and connecting the extension cable in its place.
(The existing thermistor is no longer required.)
Models for remote sensor application
Remote sensor
Extension cable (2-core)
Sensor box mounting
screws (×2)(M4×16)
Double-sided tape (×2)
Round crimp terminals
Ties (×2)
Mounting screw
Sensor box cover
Sensor box
2-M4
32
42
Wall surface mounting holes
Содержание D-BACS
Страница 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Страница 17: ...xvi 1 5 Open Network Glossary Introduction ...
Страница 41: ...24 Outline of D BACS System ...
Страница 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Страница 88: ...3 6 Wired Remote Controller with Weekly Schedule Timer BRC1D61 71 Remote Controllers 3P107422 3D ...
Страница 102: ...5 2 Wireless Remote Controller BRC4C 7C 7E 85 Remote Controllers 5 2 Wireless Remote Controller BRC4C 7C 7E ...
Страница 103: ...86 5 3 Simplified Remote Controller BRC2C51 BRC2A51 Remote Controllers 5 3 Simplified Remote Controller BRC2C51 BRC2A51 ...
Страница 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Страница 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Страница 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Страница 215: ...198 3 8 Wiring Example intelligent Manager ...
Страница 235: ...218 Interface for Use in BACnet ...
Страница 249: ...232 7 1 Node Objects Interface for use in LONWORKS 7 Object Details 7 1 Node Objects 7 2 DIII NET Common Objects ...
Страница 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Страница 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Страница 285: ...268 1 6 Notes Power Proportional Distribution P P D ...
Страница 319: ...302 1 5 Dio Unit DEC102A51 Adaptor 1 5 2 Part Names and Functions 1 Appearance Dio Unit DEC102A51 ...
Страница 329: ...312 1 6 Di Unit DEC101A51 Adaptor 1 6 2 Part Names and Functions 1 Appearance Di Unit DEC101A51 ...