3.2 Main Specifications and Functions of the Equipment
Outline of D-BACS System
Note) Central control units such as central remote controller cannot be used at the same time.
Control Method
Objective / Use
Unit Name and
Model
Function
Standard Number of
Controllers
Building Control
System
Building control
computer,
air-conditioning
control computer
and control
system for
air-conditioning
are carried out by
communication
and contact
signal.
Interface for
use in BACnet
®
DMS502B51
Optional DIII
board
DAM411A1
Optional Di
Board
DAM412A1
Parallel
interface
DPF201A51, 52, 53
Interface for
use in
LONWORKS
®
DMS504B51
Interface for use in BACnet
®
Interface unit to allow communications
between VRV and BMS.
Parallel interface
Carries out operation and monitoring function
of each indoor unit by contact and analog
signal.
Interface for use in LONWORKS
®
The LON Gateway functions as the interface for
a building monitoring system and cannot be w-
installed on the DIII-NET along with following
equipment / devices that have similar functions.
Interface for use in
BACnet
®
:
Up to 256 indoor
units (256groups)
When the option DIII
board is used
Parallel Interface,
Interface for use in
LONWORKS
®
Up to 64 indoor units
(64 groups)
Power Proportional
Distribation (P.P.D)
Performs
monitoring of
accumulated
charges and
operation for each
indoor unit.
Intelligent Touch
Controller
i-Manager III
intelligent
Touch
Controller
(Proportional
division
software is
used)
Air conditioning charges are accumulated for
each indoor unit.
Registration can be made for each tenant.
Operation/stop/abnormality monitoring for an
indoor unit is available for each tenant.
A charge
management unit
can cover 64 indoor
units.
A
dapt
or
Wiring adaptor for
electrical
appendices (2)
For control by
operation
command from
BAS
With remote
temperature
setting
KRP4A51
KRP4A52
KRP4A53
KRP4A54
Built into indoor
unit
Normally open or momentary open type
contactor
12~24 VDC or no-voltage
Various control methods available by mode
select switch
Voltage, no-voltage selector switch
Alarm and operation display signal (no-
voltage)
Selector switch of zone/individual of alarm
display
Remote temperature setting (resistance input
of 0~135
Ω
)
Selector switch for remote controller
temperature setting enable/inhibit
∗
For group unified control, the setting becomes
the same for all connected indoor units, and
each indoor unit is controlled individually by
built-in thermostat.
∗
In case of using wiring adaptor for Electrical
Appendices (2), the control by 2 remote
controller is not available.
Function is the same as above.
Used only when 3 groups or more of HRV are
interlocked and operated.
∗
In case of integrated zone control, settings for
all indoor units connected to respective
groups become the same, and each indoor
unit is controlled by built-in thermostats.
1 PC board controls
1 indoor unit.
1 PC board
simultaneously
controls 1 group of
indoor units (max. 16
units).
Wiring adaptor for
electrical
appendices (1)
With remote
temperature
setting
KRP2A53
KRP2A61
KRP2A62
Built into indoor
unit
1 adaptor could
control a maximum
of 64 groups with 1
group consisting of a
maximum of 16 units
(up to 126 units in
total).
Adaptor for wiring
When controlling
operation with
optional
accessories added
inside indoor units,
the status is
displayed outside.
Built into indoor unit
KRP1B56, 57, 59, 61
KRP1C3
Necessary when electric heater and
humidifier are incorporated optionally
Operation indicating signal is made by taking
out compressor operation signal.
1 adaptor controls
electric heaters and
humidifiers.
Adaptor for
connection with
optional
controllers for
centralized control
For controlling all
indoor units from
one place
Unification
adaptor for
computerized
control
DCS302A52
Interface
adaptor for
SkyAir series
DTA102A52
Wiring adaptor
for other air
conditioners
DTA103A51
Unification adaptor for computerized control
allows you to simultaneously turn indoor units
connected to the central remote controller on
or off or display at the central monitor panel,
etc.
Interface adaptor for SkyAir series, wiring
adaptor for other air conditioners and wiring
adaptor for ‘H’ indoor unit are for connection of
optional controllers for centralized control.
Simultaneously controls
by one unification adaptor
for computerized control,
all indoor units connected
to a central remote
controller.
Controls one indoor unit by
one interface adaptor for
SkyAir series, wiring
adaptor for other air
conditioners, and wiring
adaptor for ‘G(J)’ indoor
unit.
Содержание D-BACS
Страница 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Страница 17: ...xvi 1 5 Open Network Glossary Introduction ...
Страница 41: ...24 Outline of D BACS System ...
Страница 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Страница 88: ...3 6 Wired Remote Controller with Weekly Schedule Timer BRC1D61 71 Remote Controllers 3P107422 3D ...
Страница 102: ...5 2 Wireless Remote Controller BRC4C 7C 7E 85 Remote Controllers 5 2 Wireless Remote Controller BRC4C 7C 7E ...
Страница 103: ...86 5 3 Simplified Remote Controller BRC2C51 BRC2A51 Remote Controllers 5 3 Simplified Remote Controller BRC2C51 BRC2A51 ...
Страница 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Страница 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Страница 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Страница 215: ...198 3 8 Wiring Example intelligent Manager ...
Страница 235: ...218 Interface for Use in BACnet ...
Страница 249: ...232 7 1 Node Objects Interface for use in LONWORKS 7 Object Details 7 1 Node Objects 7 2 DIII NET Common Objects ...
Страница 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Страница 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Страница 285: ...268 1 6 Notes Power Proportional Distribution P P D ...
Страница 319: ...302 1 5 Dio Unit DEC102A51 Adaptor 1 5 2 Part Names and Functions 1 Appearance Dio Unit DEC102A51 ...
Страница 329: ...312 1 6 Di Unit DEC101A51 Adaptor 1 6 2 Part Names and Functions 1 Appearance Di Unit DEC101A51 ...