346
2.5 <DTA103A51> Wiring Adaptor for Other Air Conditioners
Adaptor
<Monitor Input>
Wire as explained here following, depending on whether input carries a voltage (VOLT.) or not (NON VOLT.). Make the
VOLT/NON VOLT. setting at the monitor input changeover switch (SS1).
(For Voltage Charged Input)
Set the monitor input changeover switch to VOLT. (Factory set: VOLT.)
(For Non Voltage Input)
Set the monitor input changeover switch to NON VOLT. (Factory set: VOLT.)
Switch the malfunction signal switch (SS3) according to needs (Factory set: W/O [OFF]). Set the switch to W (ON) to
display errors even if no operation feedback from the indoor unit is available, for example, when power to the indoor
unit is OFF. Together, set the individual switch (SS2) to OFF (ON).
Note:
This switch is ineffective when SS2 is set to ON (OFF).
The optional controller display will change, as shown on the right, depending on the monitor input state and the
malfunction signal switch (SS3) setting.
After switching the optional controller from stop to operation, it will take from 10 to 30 seconds before the optional
controller display will indicate an error.
2PA53853
(SS3) Malfunction
Signal
Optional Controller Display at Command Output
Monitor Input State
Operation Input ON
Operation Input OFF
Error Input ON
W
Operation Display
Error (A1 Display)
Error (A1 Display)
W/O
Operation Display
Connect
control input to
the common
contact
(nonpolarized).
Equipment
F1F2
BMS
Equipment
F1F2
BMS
Содержание D-BACS
Страница 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Страница 17: ...xvi 1 5 Open Network Glossary Introduction ...
Страница 41: ...24 Outline of D BACS System ...
Страница 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Страница 88: ...3 6 Wired Remote Controller with Weekly Schedule Timer BRC1D61 71 Remote Controllers 3P107422 3D ...
Страница 102: ...5 2 Wireless Remote Controller BRC4C 7C 7E 85 Remote Controllers 5 2 Wireless Remote Controller BRC4C 7C 7E ...
Страница 103: ...86 5 3 Simplified Remote Controller BRC2C51 BRC2A51 Remote Controllers 5 3 Simplified Remote Controller BRC2C51 BRC2A51 ...
Страница 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Страница 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Страница 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Страница 215: ...198 3 8 Wiring Example intelligent Manager ...
Страница 235: ...218 Interface for Use in BACnet ...
Страница 249: ...232 7 1 Node Objects Interface for use in LONWORKS 7 Object Details 7 1 Node Objects 7 2 DIII NET Common Objects ...
Страница 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Страница 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Страница 285: ...268 1 6 Notes Power Proportional Distribution P P D ...
Страница 319: ...302 1 5 Dio Unit DEC102A51 Adaptor 1 5 2 Part Names and Functions 1 Appearance Dio Unit DEC102A51 ...
Страница 329: ...312 1 6 Di Unit DEC101A51 Adaptor 1 6 2 Part Names and Functions 1 Appearance Di Unit DEC101A51 ...