228
4.1 Overview of Functions
Interface for use in LONWORKS
®
4. Function
4.1
Overview of Functions
Function
Description
Cont
rol
ling
i
tem
s
ON/OFF Command
Starts/stops air conditioner operation.
Operation Mode Setting
Sets operation mode (heating/cooling/ventilation/auto).
Temperature Setting
Sets room temperature.
Airflow Rate Setting
Sets airflow rate.
Filter Sign Reset
Resets filter sign.
Forced Thermostat OFF Setting
Sets forced thermostat OFF.
Remote ON/OFF Control Rejection
Sets whether permit/prohibit ON/OFF control rejection of the air conditioner with a
hand-held remoter controller.
Remote Operation Mode Control Rejection
Sets whether permit/prohibit operation mode control rejection of the air conditioner
with a hand-held remote controller.
Remote Temperature Setting Control
Rejection
Sets whether permit/prohibit room temperature setting control rejection of the air
conditioner with a hand-held remote controller.
System Forced OFF Setting
Forcibly stops the air conditioner connected to the DIII-NET /Resets the Forced OFF
setting.
Sub Group Address Control Rejection Setting Permits/prohibits controlling of the centralized device connected to the DIII-NET.
M
oni
tori
ng i
tem
s
ON/OFF Status Report
Monitors ON/OFF status of the air conditioner.
Operation Mode Status Report
Monitors operation mode status (heating/cooling/ventilation) of the air conditioner.
Temperature Setting Report
Monitors the set room temperature.
Room Temperature Report
Monitors the room temperature.
Airflow Rate Setting Report
Monitors the set airflow rate.
Filter Sign Report
Checks limits of filter use and monitors if it has reached the limit.
Error Status Report
Monitors error status of the air conditioners.
Error Code Report
Displays the manufacturer-specified error codes if any errors occur.
Thermostat Status Report
Monitors whether the air conditioner's thermostat is working.
Forced Thermostat OFF Setting Status
Report
Monitors the forced thermostat OFF status.
Remote ON/OFF Operation Rejection Report Monitors the status if the air conditioner is permitting/prohibiting remote ON/OFF
control with a hand-held controller.
Remote Control Operation Mode Setting
Rejection Report
Monitors the status if the air conditioner is permitting/prohibiting remote control
operation mode with a hand-held controller.
Remote Control Temperature Setting
Operation Rejection Report
Monitors the status if the air conditioner is permitting/prohibiting remote control
temperature setting with a hand-held controller.
System Forced OFF Setting Report
Monitors the status of the forced OFF setting of the air conditioner connected to the
DIII-NET.
Sub Group Address Control Operation
Rejection Setting Report
Monitors the status if the air conditioner is permitting/prohibiting control of a
centralized device connected to the DIII-NET.
A/C Communication Status Report
Monitors the communication status (No Occupancy/ Communication normal/
Communication error) of the air conditioner.
Содержание D-BACS
Страница 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Страница 17: ...xvi 1 5 Open Network Glossary Introduction ...
Страница 41: ...24 Outline of D BACS System ...
Страница 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Страница 88: ...3 6 Wired Remote Controller with Weekly Schedule Timer BRC1D61 71 Remote Controllers 3P107422 3D ...
Страница 102: ...5 2 Wireless Remote Controller BRC4C 7C 7E 85 Remote Controllers 5 2 Wireless Remote Controller BRC4C 7C 7E ...
Страница 103: ...86 5 3 Simplified Remote Controller BRC2C51 BRC2A51 Remote Controllers 5 3 Simplified Remote Controller BRC2C51 BRC2A51 ...
Страница 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Страница 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Страница 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Страница 215: ...198 3 8 Wiring Example intelligent Manager ...
Страница 235: ...218 Interface for Use in BACnet ...
Страница 249: ...232 7 1 Node Objects Interface for use in LONWORKS 7 Object Details 7 1 Node Objects 7 2 DIII NET Common Objects ...
Страница 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Страница 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Страница 285: ...268 1 6 Notes Power Proportional Distribution P P D ...
Страница 319: ...302 1 5 Dio Unit DEC102A51 Adaptor 1 5 2 Part Names and Functions 1 Appearance Dio Unit DEC102A51 ...
Страница 329: ...312 1 6 Di Unit DEC101A51 Adaptor 1 6 2 Part Names and Functions 1 Appearance Di Unit DEC101A51 ...