1.10 Functions
Interface for Use in BACnet
®
1.10
Functions
1.10.1 Air Conditioner Monitor / Control Items
The table below lists the air conditioner items that can be monitored and controlled via the BACnet communication.
Note :
1. The room temperature is measured with the suction air. Since the indoor unit fan stops when the thermostat is
disabled or the air conditioner is stopped, or in a special operation such as defrosting, temperature measurement may
be affected by the heat exchanger, and may detect and transmit a different temperature from the actual room
temperature.
For this reason, this value should be considered as a reference for the room temperature.
If the building management system manufacturer uses this value for system control (e.g., switching the air-
conditioning mode or preset temperature), the manufacturer must take on the whole responsibility.
2. The air conditioner saves the settings for the temperature, start / stop status, air-conditioning mode, air direction, and
air flow rate in the nonvolatile memory each time they are changed, so that the settings will not be lost when a power
cut occurs.
This nonvolatile memory has a write count limit and may cause a failure if it is written exceeding the limit count.
Therefore when the temperature, start / stop status, air-conditioning mode, air direction, and air flow rate of each
indoor unit are automatically controlled from the central monitoring panel, be sure that the number of changes for each
setting should not exceed 7,000 times per year.
Function
Description
M
oni
tor
Start / stop status
Monitors the start / stop status of the air conditioner.
Alarm
Monitors whether or not the air conditioner is operating normally, and issues an alarm if
the air conditioner has a malfunction.
Malfunction code
Displays a malfunction code specified by the manufacturer if an air conditioner in the
system has a malfunction.
Air-conditioning mode
Monitors if the air conditioner is cooling, heating, or ventilating.
Room temperature (Note 1)
Monitors and displays the room temperature.
Filter sign
Checks if the filter is clogged and monitors whether or not it can still be used.
Thermostat status
Monitors whether or not the air conditioner is properly controlling the temperature.
Compressor status
Monitors if the compressor of the outdoor unit connected to the indoor unit is properly
operating.
Indoor fan status
Monitors if the indoor unit's fan is properly operating.
Heater operation status
Monitors if the indoor unit's heater is properly operating.
Accumulated power
Outputs indoor unit's accumulated power consumption.
Oper
at
ion,
con
fi
gurat
ion,
and m
oni
tori
ng
Start / stop operation (Note 2)
Starts / stops the air conditioner and monitors the result.
Air-conditioning mode setting (Note 2)
Sets the cooling / heating / ventilating / auto air-conditioning mode and monitors the
result.
Room temperature setting (Note 2)
Sets the room temperature of the air conditioner and monitors the result.
Filter sign and reset
Checks if the filter is clogged and resets the status as required.
Remote controller enable / disable
Enables or disables the remote controller so that it can or cannot be used to control the
air conditioner's start / stop / air-conditioning mode / room temperature.
Lower central device operation enable /
disable
Enables or disables operation of a central device connected to the DIII-NETwork.
Air flow rate setting (Note 2)
Sets the air flow rate and monitors the result.
Air direction setting (Note 2)
Sets the air direction and monitors the result.
Forced system stop
In response to the forced stop command, checks whether clearance or setting is required
and performs the required action.
Forced thermostat disable
In response to the forced thermostat disable command, checks whether clearance or
setting is required and performs the required action.
Energy saving
In response to the energy saving command, checks whether clearance or setting is
required and performs the required action.
Содержание D-BACS
Страница 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Страница 17: ...xvi 1 5 Open Network Glossary Introduction ...
Страница 41: ...24 Outline of D BACS System ...
Страница 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Страница 88: ...3 6 Wired Remote Controller with Weekly Schedule Timer BRC1D61 71 Remote Controllers 3P107422 3D ...
Страница 102: ...5 2 Wireless Remote Controller BRC4C 7C 7E 85 Remote Controllers 5 2 Wireless Remote Controller BRC4C 7C 7E ...
Страница 103: ...86 5 3 Simplified Remote Controller BRC2C51 BRC2A51 Remote Controllers 5 3 Simplified Remote Controller BRC2C51 BRC2A51 ...
Страница 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Страница 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Страница 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Страница 215: ...198 3 8 Wiring Example intelligent Manager ...
Страница 235: ...218 Interface for Use in BACnet ...
Страница 249: ...232 7 1 Node Objects Interface for use in LONWORKS 7 Object Details 7 1 Node Objects 7 2 DIII NET Common Objects ...
Страница 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Страница 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Страница 285: ...268 1 6 Notes Power Proportional Distribution P P D ...
Страница 319: ...302 1 5 Dio Unit DEC102A51 Adaptor 1 5 2 Part Names and Functions 1 Appearance Dio Unit DEC102A51 ...
Страница 329: ...312 1 6 Di Unit DEC101A51 Adaptor 1 6 2 Part Names and Functions 1 Appearance Di Unit DEC101A51 ...