214
1.11 Backup Systems for Troubles
Interface for Use in BACnet
®
1.11
Backup Systems for Troubles
1.11.1 Failure in the System and its Backup Operation
Note :
1. ( ) indicates that backup operation of all or part of functions within the scope of influence by equipment failure is
possible.
“Corresponding group” is a group of air-conditioner controlled by local remote controller, where the failure is occurred.
“Corresponding system” is a group of air-conditioner controlled by Interface for use in BACnet
®
, where the failure is
occurred.
2. The chance that all local remote controllers and Interface for use in BACnet
®
becomes out of order is almost
negligible, so that the case is not included in the above.
Place of failure
Scope of
influence by
failure (Note 1)
Operation when failure occurs.
(description of backup)
Central
monitoring
panel
Interface
for use in
BACnet
®
Central
remote
controller
Local
remote
controller
Air-
conditioning
unit
1
{
{
{
{
✕
Corresponding
air-conditioning
unit
Corresponding air-conditioning unit is shut-down. The
details of failure is converted into code and transferred
to the central monitoring panel by the status change
notification system. The contents of failure is
displayed on local remote controller or central remote
controller.
2
{
{
{
✕
{
(Corresponding
group)
Operation, setting and monitoring is not possible by
local remote controller. Disconnect the power of the
indoor unit once and turn the power on again, so that
the backup operation is carried out by central remote
controller.
3
{
{
✕
{
{
(Corresponding
system)
Operation, setting and monitoring is not possible by
the central remote controller. The backup operation is
carried out by central monitoring panel or local remote
controller.
4
{
{
{
{
{
(Corresponding
system)
Operation, setting and monitoring is not possible by
central monitoring panel. Central remote controller
and local remote controller can backup the operation.
5
{
✕
{
{
{
(Corresponding
system)
Operation, setting and monitoring is not possible by
central monitoring panel. Central remote controller
and local remote controller can backup the operation.
6
✕
{
{
{
{
(Entire system)
Operation, setting and monitoring is not possible by
central monitoring panel. Central remote controller
and local remote controller can backup the operation.
7
{
{
✕
✕
{
(Corresponding
system)
Operation, setting and monitoring is not possible by
central remote controller and local remote controller.
Disconnect the power of the indoor unit once and turn
the power on again, so that the backup operation is
carried out by central remote controller.
8
{
{
✕
{
{
(Corresponding
system)
Operation, setting and monitoring is not possible by
central monitoring panel and the central remote
controller. The backup operation is carried out by local
remote controller.
9
Communication line between indoor unit and local
remote controller is shorted or disconnected.
(Corresponding
group)
Operation, setting and monitoring is not possible by
local remote controller. Disconnect the power of the
indoor unit once and turn the power on again, so that
the backup operation is carried out by central remote
controller.
10 Communication line between Interface for use in
BACnet
®
and indoor unit is shorted or disconnected.
(Corresponding
system)
Operation, setting and monitoring is not possible by
central monitoring panel and the central remote
controller. The backup operation is carried out by local
remote controller.
11 Communication line between Interface for use in
BACnet
®
is shorted or disconnected.
(Entire system)
Operation, setting and monitoring is not possible by
central monitoring panel. Central remote controller
and local remote controller can backup the operation.
Содержание D-BACS
Страница 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Страница 17: ...xvi 1 5 Open Network Glossary Introduction ...
Страница 41: ...24 Outline of D BACS System ...
Страница 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Страница 88: ...3 6 Wired Remote Controller with Weekly Schedule Timer BRC1D61 71 Remote Controllers 3P107422 3D ...
Страница 102: ...5 2 Wireless Remote Controller BRC4C 7C 7E 85 Remote Controllers 5 2 Wireless Remote Controller BRC4C 7C 7E ...
Страница 103: ...86 5 3 Simplified Remote Controller BRC2C51 BRC2A51 Remote Controllers 5 3 Simplified Remote Controller BRC2C51 BRC2A51 ...
Страница 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Страница 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Страница 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Страница 215: ...198 3 8 Wiring Example intelligent Manager ...
Страница 235: ...218 Interface for Use in BACnet ...
Страница 249: ...232 7 1 Node Objects Interface for use in LONWORKS 7 Object Details 7 1 Node Objects 7 2 DIII NET Common Objects ...
Страница 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Страница 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Страница 285: ...268 1 6 Notes Power Proportional Distribution P P D ...
Страница 319: ...302 1 5 Dio Unit DEC102A51 Adaptor 1 5 2 Part Names and Functions 1 Appearance Dio Unit DEC102A51 ...
Страница 329: ...312 1 6 Di Unit DEC101A51 Adaptor 1 6 2 Part Names and Functions 1 Appearance Di Unit DEC101A51 ...