120
intelligent Touch Controller
Concerning E-mail settings
An additional function to signal abnormalities on an air conditioner is available, taking advantage of the web-based
features.
* The E-mail service requires a separate mail server.
Title
Description
Remarks
E-mail settings
Using this option, any abnormality (*1) detected by the Ve-up controller is sent to a pre-
registered administrator by E-mail. The details of the error, such as the date of occurrence and
error codes, are sent by E-mail to a maximum of three addresses.
*1: "Abnormality" refers to an error affecting an air conditioner and the system facility. E-mail
message transmission is disabled if a communication error occurs between the Ve-up
controller and an air conditioner or system facility.
In addition, if an air conditioner alarm is handled as an abnormality by settings specified
during a trial run, a mail message is sent upon the occurrence of an abnormality or alarm.
The following devices are required to use the E-mail function:
Simple Mail Transfer Protocol (SMTP) server
A RFC821 compliant server which allows the transfer of E-mail messages
E-mail receiver terminal
A RFC822 compliant terminal that allows E-mail messages to be received
Note: To use the E-mail function, a network setting must be specified. E-mail messages are
not received on a receiver terminal unless a network setting is specified. (The
DCS601C1 operating manual describes details of network settings.)
The following settings must be specified on this system:
The following figure shows an example of system composition:
SMTP server
Internet
E-mail receiving terminal
Ethernet
(10BASE-T)
E-mail message
is sent upon
abnormality
intelligent touch
controller
Setting item
Description
E-mail function valid/invalid
Mail messages are not sent if "invalid" is
specified.
SMTP
Server
SMTP server address
Specify the URL (IP address) of the
SMTP server.
SMTP server port number
Specify the port number of the SMTP
server
"POP before SMTP" function
Specify whether to access a specified
POP server before sending a mail
message.
When the
"POP
before
SMTP"
function is
valid
POP Server address
Specify the URL (IP address) of the
SMTP server.
POP Server port No. Specify port number of the SMTP server
POP user ID
User ID used for POP authentication
POP passward
Password used for POP authentication
Transmitting
condition
Transmission target group
Upon failure, specify the target group to
which to send messages.
Transmission interval
If failure continues without being
resolved, a mail message is sent at
specified intervals. (Setting range: From
1 to 72 hours at 1-hour intervals)
identification name of the
intelligent touch controller
Specify the character strings to be
displayed as a title when receiving a
message.
E-mail addresses 1, 2, and 3
Specify an E-mail address. This is
omissible.
Содержание D-BACS
Страница 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Страница 17: ...xvi 1 5 Open Network Glossary Introduction ...
Страница 41: ...24 Outline of D BACS System ...
Страница 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Страница 88: ...3 6 Wired Remote Controller with Weekly Schedule Timer BRC1D61 71 Remote Controllers 3P107422 3D ...
Страница 102: ...5 2 Wireless Remote Controller BRC4C 7C 7E 85 Remote Controllers 5 2 Wireless Remote Controller BRC4C 7C 7E ...
Страница 103: ...86 5 3 Simplified Remote Controller BRC2C51 BRC2A51 Remote Controllers 5 3 Simplified Remote Controller BRC2C51 BRC2A51 ...
Страница 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Страница 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Страница 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Страница 215: ...198 3 8 Wiring Example intelligent Manager ...
Страница 235: ...218 Interface for Use in BACnet ...
Страница 249: ...232 7 1 Node Objects Interface for use in LONWORKS 7 Object Details 7 1 Node Objects 7 2 DIII NET Common Objects ...
Страница 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Страница 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Страница 285: ...268 1 6 Notes Power Proportional Distribution P P D ...
Страница 319: ...302 1 5 Dio Unit DEC102A51 Adaptor 1 5 2 Part Names and Functions 1 Appearance Dio Unit DEC102A51 ...
Страница 329: ...312 1 6 Di Unit DEC101A51 Adaptor 1 6 2 Part Names and Functions 1 Appearance Di Unit DEC101A51 ...