1.5 Dio Unit (DEC102A51)
307
Adaptor
1.5.4 Electric Wiring Work and Initial Setting
1. Electric Wiring Work
2. Initial setting
z
DEC102A51 Switch Settings
Note:
1. All are set to "OFF" upon shipment from factory.
2. *1 If operating feedback input is not detected within 10 seconds after 1 operation input is received, it results in start/
stop failure.
Name
Operation
OFF
ON
SS1
Output switching
Switching control output
Always output
"1"
Always output
“2”
DS2
Abnormal input detection Open/Close
Failure detection
Open: Close (Normal)
→
Open (Abnormal)
Close: Open (Normal)
→
Close (Abnormal)
Open
Close
DS3
Buzzer output ON/OFF
ON/OFF switching of buzzer output of
buzzer unit upon detection of failure.
ON
OFF
DS4-1
Instantaneous automatic recovery
Recover control output after power failure
to status before the power failure.
No
Yes
DS4-2
Transmission failure
Shut off control output upon detecting
transfer failure.
Yes
No
DS4-3
Later operation priority
Allowing start/stop control from facility.
Yes
No
DS4-4
Start/stop failure
Detecting start/stop failure. (*1)
No
Yes
DS5
Abnormal output shutoff/retain
Shut off control output upon detecting
failure.
Yes
No
DS6-1
Startup failure
Masking time after detecting operation
input.
10 seconds
30 seconds
DS6-2
Failure detection
Operation upon recovery from failure.
Automatic
reset
Retained
DS6-3
Monitor input
Detecting failure under halting status.
Yes
No
DS6-4
Forced termination
Ignoring forced stop signal.
No
Yes
1
7
6
3
2
5
ON
4
8
1
7
6
3
2
5
4
1
3
2
4
8
ON
ON
DS6
Ins.
SS1
Con.
Contactor
DS5
DS4
RS1 Low
DS1 High
Group No. Set
0
DS2
DS3
D4
D2
D3
D1
CD
Aiarm
Monitor
(RED)
Operation
Monitor
(GRN)
H11P H12P
2
H3P
1
H10P
3
H9P
4
INPUT
H2P
H4P
H1P
M4
A1
M3
A3
CA
M2
A2
M1
A4
CM
L
N
F1
F2
X4M
TNc4
TNa2
AC200V
~240V
TNb3
TNc1
X1M
X3M
LED10
RED
TNc3
TNa1
TNb4
TNb2
HAP
HAP
GRN
TNc2
TP1
H10P
X2M
TNa4
TNa3
TNb1
X2A
X1A
YE
RED
1
2
3
4
No simultaneous clamping is allowed for high-voltage wiring
<power supply wiring (L/N), earth wiring, relay output wiring
(CD, D1 to 4)>, low-voltage wiring <communication wiring (F1/F2),
operation input wiring (CM, M1 to 4) and abnormal input wiring
(CA, A1 to 4)> since malfunctioning may result.
Also, in case where the wirings described above are routed in parallel,
be sure to connect the wirings at least 50mm apart from the other.
To 1~200-240V and earth
To facility equipment
To facility equipment
To terminals F1, F2 of the centralized control equipment or terminals
F1, F2 of other equipment
(outdoor unit, DEC101A51, 102A51)
Содержание D-BACS
Страница 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Страница 17: ...xvi 1 5 Open Network Glossary Introduction ...
Страница 41: ...24 Outline of D BACS System ...
Страница 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Страница 88: ...3 6 Wired Remote Controller with Weekly Schedule Timer BRC1D61 71 Remote Controllers 3P107422 3D ...
Страница 102: ...5 2 Wireless Remote Controller BRC4C 7C 7E 85 Remote Controllers 5 2 Wireless Remote Controller BRC4C 7C 7E ...
Страница 103: ...86 5 3 Simplified Remote Controller BRC2C51 BRC2A51 Remote Controllers 5 3 Simplified Remote Controller BRC2C51 BRC2A51 ...
Страница 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Страница 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Страница 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Страница 215: ...198 3 8 Wiring Example intelligent Manager ...
Страница 235: ...218 Interface for Use in BACnet ...
Страница 249: ...232 7 1 Node Objects Interface for use in LONWORKS 7 Object Details 7 1 Node Objects 7 2 DIII NET Common Objects ...
Страница 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Страница 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Страница 285: ...268 1 6 Notes Power Proportional Distribution P P D ...
Страница 319: ...302 1 5 Dio Unit DEC102A51 Adaptor 1 5 2 Part Names and Functions 1 Appearance Dio Unit DEC102A51 ...
Страница 329: ...312 1 6 Di Unit DEC101A51 Adaptor 1 6 2 Part Names and Functions 1 Appearance Di Unit DEC101A51 ...