250
12.6 Monitoring and Control Restrictions
Interface for use in LONWORKS
®
12.6.3 LON Address Table Restrictions
- The entry numbers in the address tables used to bind the network variables are limited to a maximum of 15. This must
be taken into consideration when using several parameters upon binding.
12.6.4 Suspension of Message Transmission when Receiving Set Node Mode Online
- The Interface for LONWORKS
®
suspends spontaneous message transmission, such as reports of the bound output
network variable changes and heartbeat, as well as responding to the Node Object, for one minute after receiving “Set
Node Mode Online”, a management message. However, it responds to other network management requests such as
“poll” and “fetch”. This function is a mechanism to prevent time out errors because of transmission of messages
spontaneously issued by the Interface for LONWORKS
®
when it comes online due to use of an installation tool such
as the LonMaker during commissioning.
12.6.5 Group Binding Restrictions
- It is impossible to bind one of the LON monitoring node output network variables and more than one input network
variable in the Interface for LONWORKS
®
. For example, setting one of the output networks of the monitoring node at
‘ON’ cannot turn the A/C units in the 10 groups under the LON monitoring node ‘ON’.
This restriction is based on the LON regulations.
12.6.6 Prohibition Time of Commands from LON (central monitoring panel) when Power is
Restored after Power to A/C Units is Cut
- After restoration of electrical power that was cut to A/C units, commands must be sent from the LON (central
monitoring panel) at least 5 or so minutes after the restoration. A/C communications are initialized for approximately 5
minutes upon power restoration and, thus, the A/C units will not receive any commands from the LON during this time
period.
12.6.7 Room Temperature Report
As the indoor fan stops when the operation is in special operation mode such as thermostat off, at rest or defrosting, the
'Room Temperature Report' is affected by the heat exchanger and the sensor may happen to detect the temperature
different from that of the indoor and transmit the signal.
Due to the above mentioned reason, consider the temperature as a rule of thumb. If the system control is to be based on
this temperature (such as changeover of operation mode and changing the set temperature), the manufacturer of the
building management system is kindly requested to carry out on its own responsibility.
12.6.8 Change of Settings
The system is designed to keep the memory of the set conditions even when the air conditioner stops due to a power
failure. Each time when the setting of temperature, ON / OFF, heat / cool mode, or air volume is changed, it is written into
the non-volatile memory. The frequency of writing the setting into the non-volatile memory is limited and if the setting is
frequently written into memory after exceeding the limit, it may cause malfunction.
Therefore, take caution so that the frequency of changing the setting of each indoor unit may not exceed 7000
times / year when changing the setting of temperature, ON / OFF, heat / cool mode, or air volume frequently by
automatic control or the like from the central monitoring panel.
Содержание D-BACS
Страница 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Страница 17: ...xvi 1 5 Open Network Glossary Introduction ...
Страница 41: ...24 Outline of D BACS System ...
Страница 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Страница 88: ...3 6 Wired Remote Controller with Weekly Schedule Timer BRC1D61 71 Remote Controllers 3P107422 3D ...
Страница 102: ...5 2 Wireless Remote Controller BRC4C 7C 7E 85 Remote Controllers 5 2 Wireless Remote Controller BRC4C 7C 7E ...
Страница 103: ...86 5 3 Simplified Remote Controller BRC2C51 BRC2A51 Remote Controllers 5 3 Simplified Remote Controller BRC2C51 BRC2A51 ...
Страница 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Страница 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Страница 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Страница 215: ...198 3 8 Wiring Example intelligent Manager ...
Страница 235: ...218 Interface for Use in BACnet ...
Страница 249: ...232 7 1 Node Objects Interface for use in LONWORKS 7 Object Details 7 1 Node Objects 7 2 DIII NET Common Objects ...
Страница 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Страница 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Страница 285: ...268 1 6 Notes Power Proportional Distribution P P D ...
Страница 319: ...302 1 5 Dio Unit DEC102A51 Adaptor 1 5 2 Part Names and Functions 1 Appearance Dio Unit DEC102A51 ...
Страница 329: ...312 1 6 Di Unit DEC101A51 Adaptor 1 6 2 Part Names and Functions 1 Appearance Di Unit DEC101A51 ...