2.1 Function
Control Devices
2. <DCS301BA61> Unified ON/OFF Controller
2.1
Function
Turns up to 16 groups of indoor units (max. 128 units) on/off (operation/stop) by individual group or all at once, and lets
you check display of operation/malfunction at the same time.
2.2
System Configuration
This unified ON/OFF controller enables individual and unified operation/stop for a maximum of 16 groups of indoor units.
With 2 to 8 unified ON/OFF controllers, individual and unified control is possible with up to a maximum 128 groups of
indoor units.
When using 1 unified ON/OFF controller
When using 2 to 8 unified ON/OFF
controllers
(This optional accessory can not be used in conjunction with wiring adaptor for electrical appendices (optional
accessory).)
The groups of indoor units are as follows:
1. One indoor unit without remote controller
For a maximum of 16 groups of indoor units (max. 128 units),
unified operation/stop or individual operation/stop can be
performed with this optional accessory. Also allows you
check operation/error display at a glance.
By combining with a central remote controller and schedule
timer, you can construct a system that matches the size and
use of the building.
Up to 8 units connectable within 1 system.
Up to 16 units in the double central control mode.
Features thin design of a mere 16mm in thickness. (Uses JIS
recessed box for 2.)
Can be used in combination with other D-BACS equipment.
Host computer
monitor panel
Forced
OFF input
Max. 128 groups
Group No.
1–00
Group No.
1–15
Group No.
2–00
Group No.
2–15
Group No.
8–00
Group No.
8–15
Stops with input to
any single unified
ON/OFF controller.
Outdoor
unit
Outdoor
unit
Outdoor
unit
Host computer
monitor panel
Unified ON/OFF
controller
Forced
OFF input
Group No.
1–00
Group No.
1–15
Outdoor
unit
Max. 16 groups
Without remote controller
Содержание D-BACS
Страница 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Страница 17: ...xvi 1 5 Open Network Glossary Introduction ...
Страница 41: ...24 Outline of D BACS System ...
Страница 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Страница 88: ...3 6 Wired Remote Controller with Weekly Schedule Timer BRC1D61 71 Remote Controllers 3P107422 3D ...
Страница 102: ...5 2 Wireless Remote Controller BRC4C 7C 7E 85 Remote Controllers 5 2 Wireless Remote Controller BRC4C 7C 7E ...
Страница 103: ...86 5 3 Simplified Remote Controller BRC2C51 BRC2A51 Remote Controllers 5 3 Simplified Remote Controller BRC2C51 BRC2A51 ...
Страница 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Страница 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Страница 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Страница 215: ...198 3 8 Wiring Example intelligent Manager ...
Страница 235: ...218 Interface for Use in BACnet ...
Страница 249: ...232 7 1 Node Objects Interface for use in LONWORKS 7 Object Details 7 1 Node Objects 7 2 DIII NET Common Objects ...
Страница 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Страница 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Страница 285: ...268 1 6 Notes Power Proportional Distribution P P D ...
Страница 319: ...302 1 5 Dio Unit DEC102A51 Adaptor 1 5 2 Part Names and Functions 1 Appearance Dio Unit DEC102A51 ...
Страница 329: ...312 1 6 Di Unit DEC101A51 Adaptor 1 6 2 Part Names and Functions 1 Appearance Di Unit DEC101A51 ...