2.1 <KRP4A51 / KRP4A52 / KRP4A53 / KRP4A54> Wiring Adaptor for Electrical Appendices (2)
331
Adaptor
Note:
1. When constant input is used for input B at position 7
~
A, the system is shut-down forcibly (Ignored input A). Constant
input cannot be used for input B at position B.
2. Refer to the followings for the outline of above functions.
Description of Functions (Outline)
Position
Function
Input A close/open
(pulse input)
Input B close/open (pulse input)
Operation
or not of
indoor
unit
From Remote controller
Operation or not of
indoor unit
From Remote
controller
7
Remote Control Rejection
ON
Rejection
OFF at close
Rejection
8
Last command Priority
ON
Acceptable
9
Remote controller OFF
Acceptable
ON
Only Stop acceptable
A
Remote controller acceptance /
rejection, OFF
permit
Acceptable
B
Last command Priority
ON
Acceptable
OFF
Acceptable
C
Position 5 + Energy Saving
Control
The same as position 5
Forced thermostat OFF at ON
D
Position 5 + Temperature Set-
Back
Setting temperature shift command at ON
E
Position 6 + Energy Saving
Control
The same as position 6
Forced thermostat OFF at ON
F
Position 6 + Temperature Set-
Back
Setting temperature shift command at ON
1. Remote Control Rejection ................................
For when you want to turn ON/OFF only by central remote controller. (ON/OFF
cannot be controlled by remote controller for indoor unit.)
2. Remote controller OFF Only Accepted ...
...
For when you want to turn ON only by the central remote controller, and turn
OFF only by remote controller for indoor unit.
3. Central Priority ...
............................................
For when you want to turn ON only by the central remote controller, and during
the set time, turn
ON/OFF
freely by remote controller for indoor unit.
4. Individual Priority (Last command priority) ...
For when you want to turn
ON/OFF
by both central remote controller and remote
controller for indoor unit.
5. Remote Controller Permission Timer ...
........
For when you want to turn
ON/OFF
by remote controller for indoor unit during
set time, and you want to start the operation by remote controller for indoor unit
at the programmed time of system start.
Содержание D-BACS
Страница 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Страница 17: ...xvi 1 5 Open Network Glossary Introduction ...
Страница 41: ...24 Outline of D BACS System ...
Страница 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Страница 88: ...3 6 Wired Remote Controller with Weekly Schedule Timer BRC1D61 71 Remote Controllers 3P107422 3D ...
Страница 102: ...5 2 Wireless Remote Controller BRC4C 7C 7E 85 Remote Controllers 5 2 Wireless Remote Controller BRC4C 7C 7E ...
Страница 103: ...86 5 3 Simplified Remote Controller BRC2C51 BRC2A51 Remote Controllers 5 3 Simplified Remote Controller BRC2C51 BRC2A51 ...
Страница 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Страница 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Страница 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Страница 215: ...198 3 8 Wiring Example intelligent Manager ...
Страница 235: ...218 Interface for Use in BACnet ...
Страница 249: ...232 7 1 Node Objects Interface for use in LONWORKS 7 Object Details 7 1 Node Objects 7 2 DIII NET Common Objects ...
Страница 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Страница 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Страница 285: ...268 1 6 Notes Power Proportional Distribution P P D ...
Страница 319: ...302 1 5 Dio Unit DEC102A51 Adaptor 1 5 2 Part Names and Functions 1 Appearance Dio Unit DEC102A51 ...
Страница 329: ...312 1 6 Di Unit DEC101A51 Adaptor 1 6 2 Part Names and Functions 1 Appearance Di Unit DEC101A51 ...