248
12.5 LON Communication Specifications
Interface for use in LONWORKS
®
(3) Send on Delta Temperature: Detect Minimum Temperature Change
The bound output network variables will be sent to notify the system when there is a change in temperature that is
greater than the above specified value between two consecutive transmissions.
(4) Delay Start Up: Transmission Start Delay Time after Start Up
The time lag between turning on the LON node and starting the LON communications. This setting is useful for
avoiding communication congestion when LON nodes on the network simultaneously start up.
(5) Range Maximum: Maximum Transmission Limit
The number of messages transmitted from the Interface for LONWORKS
®
will effectively controlled by the bound
output network variables. It also specifies the number of messages to be sent per minute. This is used to limit the
number of messages to be consecutively sent from the nodes when they are started up.
-
Items to be transmitted are the following 6 items: On/Off Status, Room Temperature, Filter Sign, Error Status,
Error Code and A/C Communication Status.
-
The Interface for LONWORKS
®
collects room temperature data every 12 seconds, so any heartbeat transmission set
at a lower time interval will ultimately result in a 12-second transmission interval.
Control items
Values and meanings
Minimum Transmission Interval
sec.
0 seconds and 1.0
-
1200.0 seconds
0: No control, Default Value: 0
Heartbeat Transmission
sec.
0 seconds and 10.0
-
1200.0
0: No control, Default Value: 0
Detect Minimum Temperature
Change
°
C
Temp. (
°
C): 0.10-10.00, Default Value: 0.10
Transmission Start Delay Time after
Start Up
sec.
60.0-1200.0, Default Value: 60.0
Maximum Transmission Limit
(messages/sec.)
--
0 and 1-6000, 0: No control, Default Value: 0
Содержание D-BACS
Страница 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Страница 17: ...xvi 1 5 Open Network Glossary Introduction ...
Страница 41: ...24 Outline of D BACS System ...
Страница 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Страница 88: ...3 6 Wired Remote Controller with Weekly Schedule Timer BRC1D61 71 Remote Controllers 3P107422 3D ...
Страница 102: ...5 2 Wireless Remote Controller BRC4C 7C 7E 85 Remote Controllers 5 2 Wireless Remote Controller BRC4C 7C 7E ...
Страница 103: ...86 5 3 Simplified Remote Controller BRC2C51 BRC2A51 Remote Controllers 5 3 Simplified Remote Controller BRC2C51 BRC2A51 ...
Страница 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Страница 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Страница 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Страница 215: ...198 3 8 Wiring Example intelligent Manager ...
Страница 235: ...218 Interface for Use in BACnet ...
Страница 249: ...232 7 1 Node Objects Interface for use in LONWORKS 7 Object Details 7 1 Node Objects 7 2 DIII NET Common Objects ...
Страница 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Страница 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Страница 285: ...268 1 6 Notes Power Proportional Distribution P P D ...
Страница 319: ...302 1 5 Dio Unit DEC102A51 Adaptor 1 5 2 Part Names and Functions 1 Appearance Dio Unit DEC102A51 ...
Страница 329: ...312 1 6 Di Unit DEC101A51 Adaptor 1 6 2 Part Names and Functions 1 Appearance Di Unit DEC101A51 ...