2.6 <KRP928B2S> Interface Adaptor for DIII-NET (RA)
Adaptor
2.6
<KRP928B2S> Interface Adaptor for DIII-NET (RA)
2.6.1 Functions
Type
BRC1C62
KRP928B2S
Group/Zone
Item
One Group
Unified control for all Zone
ON/OFF
Possible
Possible
Temp. setting
Possible
Possible
Air flow rate setting
Possible
Impossible
Air flow direction setting
Possible
Impossible
Timer setting twice a day
Possible
Impossible
Mode setting
Possible
Possible
Filter sign reset
Possible
Impossible
Inspection/Test operation
Possible
Operation display only by lamps
<Overview, Features and Compatible Models>
<Component Parts and Separately-Sold Parts which are Required>
This kit includes the following components. Check to ensure that none of these are missing.
Screw cover
Parts
Kit assy
PCB is in the housing.
Q’ty
Q’ty
1
Parts
Connection harness (about 1.6m)
Mounting screws
Binding band
Installation manual
1set
3pcs.
1pc.
1set
This kit is the interface required when connecting the central controller and a Daikin Room Air
Conditioner. Use of the central controller makes it possible to perform the following monitoring
and operations. It is compatible with room air conditioners which have an HA connector S21.
1.Run / stop for the central controller and wired remote controller, operating mode selection, and
temperature can be set.
2.The operating status, any errors, and the content of those errors can be monitored from the
central controller and wired remote controller.
3.Run / stop for the central controller and wireless remote controller, operating mode selection, and
the temperature setting can be limited by the central controller.
4.Zone control can be performed from the central controller.
5.The unit can remember the operating status of the air conditioner before a power outage and then
start operating in the same status when the power comes back on.
6.Card keys, operating control panels, and other constant / instantaneous connection-compatible
equipment can be connected.
7.The Operating / error signals can be read.
8.HA JEM-A-compatible equipment can be connected.
9.The indoor temperature can be monitored from the Ve-up controller.
Precaution
1.When reading the Operating / error signals, a separate external power source (DC 12V) is needed.
2.A separate timer power source (DC 16V) is needed when using the schedule timer independently,
and not in conjunction with other central controllers.
3.The range of temperatures that can be set from the central controller is 18
°
C to 32
°
C in cooling
and 14
°
C to 28
°
C in heating.
4.Fan operation cannot be selected from the central controller or wired remote controller.
5.Group control (i.e., control of multiple indoor units with a single remote controller) is not available.
6.Monitoring is not available of the thermo status, compressor operating status, indoor fan operating
status, electric heater, or humidifier operating status.
7.Forced thermo off, filter sign display and reset, fan direction and speed settings, air conditioning
fee management, energy savings instructions, low-noise instructions, and demand instructions
cannot be made.
Содержание D-BACS
Страница 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Страница 17: ...xvi 1 5 Open Network Glossary Introduction ...
Страница 41: ...24 Outline of D BACS System ...
Страница 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Страница 88: ...3 6 Wired Remote Controller with Weekly Schedule Timer BRC1D61 71 Remote Controllers 3P107422 3D ...
Страница 102: ...5 2 Wireless Remote Controller BRC4C 7C 7E 85 Remote Controllers 5 2 Wireless Remote Controller BRC4C 7C 7E ...
Страница 103: ...86 5 3 Simplified Remote Controller BRC2C51 BRC2A51 Remote Controllers 5 3 Simplified Remote Controller BRC2C51 BRC2A51 ...
Страница 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Страница 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Страница 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Страница 215: ...198 3 8 Wiring Example intelligent Manager ...
Страница 235: ...218 Interface for Use in BACnet ...
Страница 249: ...232 7 1 Node Objects Interface for use in LONWORKS 7 Object Details 7 1 Node Objects 7 2 DIII NET Common Objects ...
Страница 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Страница 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Страница 285: ...268 1 6 Notes Power Proportional Distribution P P D ...
Страница 319: ...302 1 5 Dio Unit DEC102A51 Adaptor 1 5 2 Part Names and Functions 1 Appearance Dio Unit DEC102A51 ...
Страница 329: ...312 1 6 Di Unit DEC101A51 Adaptor 1 6 2 Part Names and Functions 1 Appearance Di Unit DEC101A51 ...