1.6 Di Unit (DEC101A51)
313
Adaptor
The figure below shows the printed circuit board built in this equipment.
2. Specifications
Di board
Input contacts
16 points.
8 pairs based on a pair of On/Off input and abnormality input
* Contact information(On/Off, Abnormality ) is transmitted to
intelligent Touch Controller / intelligent Manager III through DIII-
Net communication.
Installation method
Indoor installation
Power supply
To be supplied from outside
Rating
AC200-240V, 50/60Hz
Applied Standard
Safety standard: IEC730, EMC standard: CISPR22-A (EMI),
CISPR24 (EMS)
Environment for use
Ambient temperature
–15 to 60 °C
Ambient humidity
95%RH or less (no condensation)
Environment for storage
Ambient temperature
–20 to 60 °C
Ambient humidity
95%RH or less (no condensation)
The power transformer connector
is connected.
Group No. Set
RS1 Low
DS1 High
0
DS2
DS3
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4
ON
DS6
ON
DS4
DS5
ON
F2
F1
TP1
H2P
H8P
H12P
Operation
Monitor
(GRN)
INPUT
H3P
5
H5P
H14P
H11P
H13P
H7P
H1P
7
H6P
Aiarm
Monitor
(RED)
H10P
H9P
4
H15P
2
1
8
3
H16P
H4P
6
CM
M7
A2
CA
M5 M6
A1
A6
A8
M4
A5
A4
A3
M1
M8
M3
M2
A7
N
L
RED
X2A
HAP
YE
GRN
X1A
X3M
X2M
X1M
AC200V
~ 240V
RED
H17P
Whether or not the abnormal condition
of facility equipment during stop is
recognized can be selected.
Microcomputer OK monitor
(LED-A: Green)
Transformer connecting connector
(CN1/CN2)
Terminal block for transmission (F1/F2)
(Terminal size: M3)
Error detecting switch
(DS6-2)
Abnormal input detecting switch
(DS2/DS3)
Connect this unit to the terminals F1, F2
of the centralized control equipment.
Transmission error monitor
(LED10: Red)
For the power supply,
use 1
~
200 - 240V.
It is possible to select whether the
error at startup is masked for
10 or 30 seconds.
The facility equipment status
is monitored.
Start error mask switch
(DS6-1)
Monitor input switch
(DS6-3)
Quantity change shortcircuit pin
(TP1)
Whether the connected equipment "error"
is detected with contact input "Open" or
"Closed" can be selected.
Terminal block for monitor input
(Terminal size: M3.5)
When the microcomputer is in
normal operation, the lamp flickers.
DIII-NET Address No. setting switch
(RS1/DS1)
It is possible to select whether the
equipment connection error is a
non-latch or latch error.
When the transmission is
abnormal, the lamp lights up,
disabling remote control.
(The lamp goes out in the
normal condition.)
Shortcircuit during control
quantity setting
Switch for selecting the number
of facility equipment connected
(DS4/DS5)
Set DIII-NET Address No.
Power supply terminal
block (L, N)
Set the switch according to the number
of facility equipment connections.
Содержание D-BACS
Страница 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Страница 17: ...xvi 1 5 Open Network Glossary Introduction ...
Страница 41: ...24 Outline of D BACS System ...
Страница 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Страница 88: ...3 6 Wired Remote Controller with Weekly Schedule Timer BRC1D61 71 Remote Controllers 3P107422 3D ...
Страница 102: ...5 2 Wireless Remote Controller BRC4C 7C 7E 85 Remote Controllers 5 2 Wireless Remote Controller BRC4C 7C 7E ...
Страница 103: ...86 5 3 Simplified Remote Controller BRC2C51 BRC2A51 Remote Controllers 5 3 Simplified Remote Controller BRC2C51 BRC2A51 ...
Страница 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Страница 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Страница 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Страница 215: ...198 3 8 Wiring Example intelligent Manager ...
Страница 235: ...218 Interface for Use in BACnet ...
Страница 249: ...232 7 1 Node Objects Interface for use in LONWORKS 7 Object Details 7 1 Node Objects 7 2 DIII NET Common Objects ...
Страница 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Страница 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Страница 285: ...268 1 6 Notes Power Proportional Distribution P P D ...
Страница 319: ...302 1 5 Dio Unit DEC102A51 Adaptor 1 5 2 Part Names and Functions 1 Appearance Dio Unit DEC102A51 ...
Страница 329: ...312 1 6 Di Unit DEC101A51 Adaptor 1 6 2 Part Names and Functions 1 Appearance Di Unit DEC101A51 ...