3.7 Setting group No. for centralized control
intelligent Manager
3.7
Setting group No. for centralized control
1P177853B
(Group numbers increase in the order of
1-00, 1-01, · · · 1-15, 2-00, · · · 8-15)
(5) Press " " to set the selected group No.
(6) Press " " to return to the NORMAL MODE.
NOTICE Be sure to keep the operation manual for maintenance.
Set the group number of each group of the indoor unit from the remote controller. (In case of no remote
controller, also connect the remote controller and set the group No. Then, remove the remote controller.)
(1) Turn ON the power of the indoor unit and intelligent Processing Unit.
(Unless the power is ON, no setting can be made.)
Check that the installation and electrical wiring are correct before turning the power supply ON.
(When the power supply is turned ON, all LCD appear once and the unit may not accept the operation
for about one minute with the display of " ".)
TEST
TEST
(2) While in the normal mode, hold down the " " button for a minimum of 4 seconds.
The remote controller will enter the FIELD SET MODE.
(3) Select the MODE No. " " with the " " button.
(4) Use the " " button to select the group No. for each group.
NOTE) · For details on making settings from the simplified remote controller, refer to the instruction manual of the unit.
· See the instruction manuals which came with the Ventiair and adapters (i.e., multi-purpose adapters) for
details on their Group No. settings.
FIELD SET
MODE
GROUP NO.
TEST
MODE NO.
SETTING
Содержание D-BACS
Страница 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Страница 17: ...xvi 1 5 Open Network Glossary Introduction ...
Страница 41: ...24 Outline of D BACS System ...
Страница 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Страница 88: ...3 6 Wired Remote Controller with Weekly Schedule Timer BRC1D61 71 Remote Controllers 3P107422 3D ...
Страница 102: ...5 2 Wireless Remote Controller BRC4C 7C 7E 85 Remote Controllers 5 2 Wireless Remote Controller BRC4C 7C 7E ...
Страница 103: ...86 5 3 Simplified Remote Controller BRC2C51 BRC2A51 Remote Controllers 5 3 Simplified Remote Controller BRC2C51 BRC2A51 ...
Страница 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Страница 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Страница 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Страница 215: ...198 3 8 Wiring Example intelligent Manager ...
Страница 235: ...218 Interface for Use in BACnet ...
Страница 249: ...232 7 1 Node Objects Interface for use in LONWORKS 7 Object Details 7 1 Node Objects 7 2 DIII NET Common Objects ...
Страница 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Страница 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Страница 285: ...268 1 6 Notes Power Proportional Distribution P P D ...
Страница 319: ...302 1 5 Dio Unit DEC102A51 Adaptor 1 5 2 Part Names and Functions 1 Appearance Dio Unit DEC102A51 ...
Страница 329: ...312 1 6 Di Unit DEC101A51 Adaptor 1 6 2 Part Names and Functions 1 Appearance Di Unit DEC101A51 ...