4.1 Functions
101
intelligent Touch Controller
4. Functions
4.1
Functions
Central control device name
intelligent Touch Controller
Product name/System name
intelligent Touch Controller main
unit alone
Use with DIII-NET Plus ADP
Model name
DCS601C51
DCDCS601A52
Function
Details
Wi
ri
ng Li
m
it
at
ions
No. of DIII lines (ports)
No. of F1/F2
1
2 (1+1)
No. of controllable indoor
units
No. of groups
64
128 (64+64)
No. of units connected (Max. No. of
units is 128 per DIII-NET line)
128
(64 when P.P.D. is conducted)
256
(128 when P.P.D. is conducted)
No. of controllable zones
1 zone --- 1 group or more
1 zone --- the same setting for all of
the indoor units.
1 zone is from 1 up to 64 groups
128
128
No. of outdoor units
No. of connected units (Max. No. of 10
units per 1 DIII-NET line)
10
10×2
Required master-slave
setting when installed in
multiple sites
Connectors, screens and switches
On screen: (Master/Slave)
Follows the settings of the
intelligent touch controller unit
Control wiring for central
settings
Determine master-slave relationship
for other central control devices
CN1 (Master central setting
connector)
CN1 (Master central setting
connector)
Necessity of power supply
Yes / Terminal block
Yes/N-L
Yes/N-L
Operat
ion
set
ups
Operation
Touch
panel
Operated via the intelligent touch
controller touch panel
Method of operation
Group
Yes
ON (OFF)
Group
Yes
Unified ON/OFF
All connected units
Yes
By group/zone
Yes
Cooling/Heating
changeover
By group/zone
Yes
Temperature setting
By group/zone
Yes
Filter sign reset
By group/zone
Yes
Vane direction change
By group/zone
Yes
Airflow rate change
By group/zone
Yes
Ventilation mode
By group/zone
Yes
(to be addressed as of the HRV 2005 [G type] model)
Ventilation rate
By group/zone
Yes
(to be addressed as of the HRV 2006 [GA type] model)
Forced OFF input
External signal: Non-voltage,
normally open contact, /Main unit
terminal block
0.75-1.25 mm
2
up to 150 m
Yes
Yes
(Forced OFF (shutdown) is input
from the contact point of the
intelligent touch controller main
body and conducted
simultaneously with shutdown
(forced OFF) of the A/C units
connected to the intelligent touch
controller unit.)
Individual remote control
rejection/acceptance
setting
By group/zone
ON/OFF, mode setting and
temperature setting
Yes
Содержание D-BACS
Страница 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Страница 17: ...xvi 1 5 Open Network Glossary Introduction ...
Страница 41: ...24 Outline of D BACS System ...
Страница 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Страница 88: ...3 6 Wired Remote Controller with Weekly Schedule Timer BRC1D61 71 Remote Controllers 3P107422 3D ...
Страница 102: ...5 2 Wireless Remote Controller BRC4C 7C 7E 85 Remote Controllers 5 2 Wireless Remote Controller BRC4C 7C 7E ...
Страница 103: ...86 5 3 Simplified Remote Controller BRC2C51 BRC2A51 Remote Controllers 5 3 Simplified Remote Controller BRC2C51 BRC2A51 ...
Страница 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Страница 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Страница 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Страница 215: ...198 3 8 Wiring Example intelligent Manager ...
Страница 235: ...218 Interface for Use in BACnet ...
Страница 249: ...232 7 1 Node Objects Interface for use in LONWORKS 7 Object Details 7 1 Node Objects 7 2 DIII NET Common Objects ...
Страница 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Страница 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Страница 285: ...268 1 6 Notes Power Proportional Distribution P P D ...
Страница 319: ...302 1 5 Dio Unit DEC102A51 Adaptor 1 5 2 Part Names and Functions 1 Appearance Dio Unit DEC102A51 ...
Страница 329: ...312 1 6 Di Unit DEC101A51 Adaptor 1 6 2 Part Names and Functions 1 Appearance Di Unit DEC101A51 ...