1.4 Conditions and Method to Exclude Calculation for Specified Indoor Unit
261
Power Proportional Distribution (P.P.D.)
1.4
Conditions and Method to Exclude Calculation for Specified Indoor Unit
There is a case that a part of indoor units is desired to be excluded from calculation, such as corridor, hall, etc..
Typically, there are two ways as below.
1.4.1 The Power Consumption of Common-use Area can be Separated from Other Areas
1.4.2 The Power Consumption of Common-use Area is Distributed to Other Area
(In this case, it cannot uniformly be distributed to other indoor units. The power consumption of the common-use section
may be added to the specific indoor unit.)
Example:
When the power consumption is A=B=C=10kW and X=Y=Z=5kW, the calculation result total is 45kW, and the calculated
value of A, B and C is as follows:
The common-use section is distributed and power consumption is more than the actual one.
• Separating the system is required among the common-
use area, outdoor units for office, etc. and the power
source.
• Enter “No” in the column of electric energy distributing in
Address Table.
* In calculating the common-use power independently, it
is also possible to mount the watthour meter (with pulse
output) for common-use area.
• The power consumption of the common-use area is
distributed to the indoor unit in the office, etc. The
calculated value in the office, etc. is increased by the
value distributed from the common-use area.
• The wiring work method for the common-use area is
quite the same as that of the indoor unit in other offices,
etc.
* Enter “No” in the column of electric energy distributing
in Address Table.
A=B=C=
10
× 45=15kW
10+10+10
A
B
C
X
Y
Z
WHM
iPU
Power source
three-phase
Electric energy
pulse signal line
Common-use area
A
B
C
X
Y
Z
WHM
Integrating watthour meter with pulse output
Power source
three-phase
Electric energy
pulse signal line
Common-use section
iPU
Содержание D-BACS
Страница 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Страница 17: ...xvi 1 5 Open Network Glossary Introduction ...
Страница 41: ...24 Outline of D BACS System ...
Страница 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Страница 88: ...3 6 Wired Remote Controller with Weekly Schedule Timer BRC1D61 71 Remote Controllers 3P107422 3D ...
Страница 102: ...5 2 Wireless Remote Controller BRC4C 7C 7E 85 Remote Controllers 5 2 Wireless Remote Controller BRC4C 7C 7E ...
Страница 103: ...86 5 3 Simplified Remote Controller BRC2C51 BRC2A51 Remote Controllers 5 3 Simplified Remote Controller BRC2C51 BRC2A51 ...
Страница 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Страница 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Страница 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Страница 215: ...198 3 8 Wiring Example intelligent Manager ...
Страница 235: ...218 Interface for Use in BACnet ...
Страница 249: ...232 7 1 Node Objects Interface for use in LONWORKS 7 Object Details 7 1 Node Objects 7 2 DIII NET Common Objects ...
Страница 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Страница 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Страница 285: ...268 1 6 Notes Power Proportional Distribution P P D ...
Страница 319: ...302 1 5 Dio Unit DEC102A51 Adaptor 1 5 2 Part Names and Functions 1 Appearance Dio Unit DEC102A51 ...
Страница 329: ...312 1 6 Di Unit DEC101A51 Adaptor 1 6 2 Part Names and Functions 1 Appearance Di Unit DEC101A51 ...