Valid values for Lower Limit range from 0% - 45%. For Upper Limit, valid
values range from 55% - 100%. For non-dimmed fixtures, upper and lower
limit values are fixed at 100% and 0%.
For 3-wire motor loads, you can select advanced motor properties.
Max Time
sets the maximum time that the motor can remain in the Open or
Close state. That is, when an "Open" or "Close" command turns the motor
on, the motor will move in the indicated direction 1) until <Max Time>
expires; 2) until another command turns the motor off; or 3) until it hits a
limit switch in the motor assembly.
Valid values for Max Time range from 10 seconds to 8 minutes. It should be
set to a value greater than the full-range travel time of the motor being
controlled.
Jog Time
sets the time that the motor will move in the Open or Close
direction during a "Jog" command. That is, a rising edge of a Jog Open or
Jog Close command will cause the motor to move in the indicated direction
for <Jog Time> seconds.