Chapter 10 Managing System Hardware
Configuring Power Supplies
You decide to change the switch to
redundant
mode. Then the current capacity decreases to
2500Watts and the configuration is rejected.
Reason: 2500Watts is less than the system usage (3000Watts).
Managing Power Supplies
To manage power supply power attributes, perform the following steps.
Step 1
From the Fabric Manager menu tree, choose
Switches > Modules
and then click the
Power Supplies
tab, or from the Device Manager, choose
Physical > Power Supplies
. The Information pane from the
Fabric Manager displays power supply power attributes for multiple switches. The dialog box from the
Device Manager displays power supply power attributes for a single switch.
Step 2
Configure the power attributes for the power supply.
Table 10-3
Summary of Configuration Scenarios for Power Supplies with Different Capacities
Scenario
Power
Supply 1
(W)
Current
Mode
Current
Usage (W)
Power
Supply 2
(W)
New Mode
New
Capacity
(W)
Action
Taken by
Switch
1
2500
combined
2000
1800
N/A
3600
Existing
configurati
on.
2500
N/A
2000
1800
redundant
2500
Power
supply 2 is
shut down
2
2500
combined
2000
2200
N/A
4400
Existing
configurati
on.
2500
N/A
2000
2200
redundant
2200
The new
capacity is
changed.
3
2500
combined
3000
1800
N/A
3600
Existing
configurati
on.
2500
N/A
3000
1800
redundant
N/A
Rejected,
so the
mode
reverts to
combined
mode.