DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
73
9M02-9249-A001-EN
Revision A
Name
Parent Menu
Range
Default
Description
Limit
Method
RapidCore only.
Engine Speed
menu.
Speed Bias
Min RPM / Max
RPM
Speed Bias
(Programmable from RapidCore
Configurator Software only)
The method in which the minimum and
maximum speeds the operator is
allowed to adjust is determined.
Speed
Bias
Sensors >
Engine Speed >
RPM Control
0 ~ 600 RPM
in 1 RPM
increments
30 RPM
The minimum or maximum RPM that
the engine speed can be adjusted
around the Rated RPM. Example:
Rated RPM is 1800 and Speed Bias is
150. The minimum RPM will be 1650
and maximum RPM will be 1950. Only
valid when the correct Limit Method is
chosen.
Min
Speed
500 ~ 4000 RPM
in 1 RPM
increments
600 RPM
The minimum RPM that can be set
using speed control. Only valid when
the correct Limit Method is chosen.
Max
Speed
500 ~ 4000 RPM
in 1 RPM
increments
2000 RPM
The maximum RPM that can be set
using speed control. Only valid when
the correct Limit Method is chosen.
TSC1
RPM/s
Sensors >
Engine Speed >
RPM Control
Disable
10 ~ 300 RPM/s
in 10 RPM/s
increments
200 RPM/s
Ignore this setting. Refer to the J1939
Reference Manual for information on
this setting.
Speed Control Instructions
When the controller is running and there are other functions occurring, the controller will scroll through its display
parameters as usual. When the speed control page is displayed, it will show the Engine Speed as well as the
following instructions: Hold AUTO + Up/Down to Adjust RPM.
Speed Control Parameter Page
Speed Control Adjust Page
Pressing and holding the AUTO button will display the screen to the right. If a
‘Display Adjust Parameter’ is set, it
will also be displayed underneath the Engine Speed. While still holding the AUTO key, press the up or down
arrows to adjust the RPM. The Engine Speed display should update as the engine physically changes its speed
to accommodate the speed request.
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...