DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
64
9M02-9249-A001-EN
Revision A
to indicate there is a warning with the AC frequency. The following table shows the output state based on the
Warnings status.
Low AC Frequency Warning
High AC Frequency Warning
Switched Output State
Inactive
Inactive
OFF
Inactive
Active
ON
Active
Inactive
ON
Active
Active
ON
5.4.2 Pull and Hold Coil
On some engine systems the fuel pump has two coils. This is because the initial power-on of the fuel solenoid
requires substantial current (Pull Coil), but only needs a small amount of current to hold it in place (Hold Coil).
1. Hold Coil (Fuel) is energized.
2. Pull Coil is energized for the first 1.6 to 1.8 seconds of preheat. If preheat is disabled, the pull coil is
energized at the beginning of cranking; the crank output turned off for that time period.
3. This is repeated for each crank attempt.
Configuring a switched output to Pull Coil automatically configures the engine logic necessary for a Pull Coil
system.
Note:
The pull coil feature does not operate when the fuel output is activated by the Auto Power ECM
feature or when requesting stored DTCs (DM2 codes). See the
information on these features.
Pull Coil Wiring Example
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...