DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
44
9M02-9249-A001-EN
Revision A
Event Name
Event Type
Description
Low Coolant Lvl
Failure
The
“Low Coolant Level” switched input is active indicating low coolant
level failure.
Over Crank
Failure
The controller exhausted the crank attempts (specified in Timers >
Engine Logic > Crank Attempts) and could not start the engine.
Over Voltage
Failure
The generator AC voltage has risen above the over voltage failure
setpoint set under AC Monitor > Genset Voltage > Setpoints.
Under Voltage
Failure
The generator AC voltage has fallen below the under voltage failure
setpoint set under AC Monitor > Genset Voltage > Setpoints.
Regen Needed
Failure
For electronic engines with a diesel particular filter (DPF) only. The
user must perform a regeneration before running the engine further.
Continuing to ignore this message could result in the DPF being
damaged and requiring replacement.
Low Air Pressure
Failure
The
“Air Press. Fail” switched input is active. Indicates a low air
pressure failure condition.
Low Hydraulic
Failure
The
“Hyd Pres. Fail” switched input is active. Indicates a low hydraulic
pressure failure condition.
High Battery
Failure
The main starter battery (the battery from which the controller is
powered) voltage has risen above the high battery failure setpoint set
under Sensors > Battery.
Loss Of ECM
Comm
Failure
For electronic engines only. The
“Loss of ECM” under J1939 must be
enabled. The controller has not detected engine speed, oil pressure,
or engine temperature on its CAN J1939 port.
Under Frequency
Failure
The generator AC frequency has fallen below the under frequency
failure setpoint set under AC Monitor > Genset Freq. > Setpoints.
Over Frequency
Failure
The generator AC frequency has risen above the over frequency
failure setpoint set under AC Monitor > Genset Freq. > Setpoints.
DPF SRVC REQ'D!
Failure
For electronic engines with a diesel particulate filter (DPF) only.
Service the DPF ASAP. Damage to the DPF is possible if the engine is
run.
SERVICE DPF!!!
Failure
For electronic engines with a diesel particulate filter (DPF) only.
Service the DFP ASAP. Damage to the DPF is likely if the engine is
run.
Calibration Fail
Failure
Doosan G2 electronic engine only. Contact Doosan for more
information.
High Fuel Temp
Failure
Doosan G2 electronic engine high fuel temperature failure. This failure
comes from the engine ECM over CAN J1939.
Hi Exhaust Temp
Failure
Doosan G2 electronic engine high turbine exhaust temperature failure.
This failure comes from the engine ECM over CAN J1939.
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...