DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
100
9M02-9249-A001-EN
Revision A
Name
Volt Select 2 Input
Genset Voltage > Auto Nominal
These settings correspond to the
“Nominal Volts” setting under the AC
Monitor > Genset Voltage menu.
Genset Voltage > Auto Scaling
These settings correspond to the
“Scaling Factor” setting under the AC
Monitor > Genset Voltage menu.
Genset Voltage > Auto Single
Only applies when voltage source is set to 1-Phase 3-Wire. This
determines the phases from which the single phase voltage is read:
A-C or A-B.
Genset Current > Auto Rated
These settings correspond to the
“Rated Amps” setting under the AC
Monitor > Genset Current menu.
Genset Current > Auto Scaling
These settings correspond to the
“Scaling Factor” setting under the AC
Monitor > Genset Current menu.
5.7.2 Generator Frequency
Generator AC frequency display on the controller is enabled when the
is not set to Disable.
The following settings are used to configure the controller
’s responses to frequency measurements.
Frequency Settings (in AC Monitor > Genset Freq)
Name
Range
Default
Description
Freq. Source
50 Hz System
(50 Hz)
60 Hz System
(60 Hz)
Auto Selection
60 Hz
System
This is the wiring configuration of the
generator. Selecting Auto Selection will
use the
input to determine which frequency is
used.
This setting is used by the following
setpoints. It does not affect the display of
AC Frequency.
Setpoints > Low Warn
(Under-Frequency
Warning)
Disable
20 ~ 99%
in 1% increments
90%
Reading at which a warning occurs.
Setpoints > Low Fail
(Under-Frequency
Failure)
Disable
20 ~ 99%
in 1% increments
85%
Reading at which a failure occurs.
Setpoints > High Warn
(Over-Frequency
Warning)
Disable
101 ~ 150%
in 1% increments
110%
Reading at which a warning occurs.
Setpoints > High Fail
(Over-Frequency
Failure)
Disable
101 ~ 150%
in 1% increments
115%
Reading at which a failure occurs.
5.7.2.1
RPM / Frequency Select
The controller has the ability to change between Primary RPM / 60 Hz and Secondary RPM / 50 Hz through the
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...