The switched outputs already contain a kickback diode. Do not connect relays with an internal kickback
diode to a switched output as the output may be shorted. This includes relays in the RelayPak
•
Fusing:
-
A fuse should be placed in line with the battery positive wire going to the controller power; a 10 A
fuse is suggested
-
The AC Voltage A, B and C lines should be fused near the source of AC voltage with a 1 A fuse to
protect personnel if any of these lines becomes disconnected or damaged
-
If using the RelayPak, the power going to the relay commons should be fused
•
For noisy environments, some guidelines are as follows:
-
Replace speed sensing wires with twisted pair from the sensor to the controller
-
Consider using isolated sensors (i.e., two terminal) and use twisted pair wiring to connect from the
engine to the controller
When possible, the following enclosure guidelines should be followed:
•
It is recommended that vibration mounts be used
•
For outdoor applications, it is recommended that a sealed enclosure be used
2.2
Terminal Descriptions
Main Connector (J4)
Terminal
Name
Description
J4-1
+Battery
Provides power to the controller from the battery
J4-2
+Battery
Provides power to the controller from the battery
J4-3
Ground
Provides ground return for the controller
J4-4
Ground
Provides ground return for the controller
J4-5
Switched Input A
Configurable to Battery, Ground, or Open
J4-6
Switched Input B
Configurable to Battery, Ground, or Open
J4-7
Switched Input C
Configurable to Battery, Ground, or Open
J4-8
Switched Output A
OBattery voltage when active (Max Current: 1 A)
J4-9
Switched Output C
OBattery voltage when active (Max Current: 1 A)
J4-10
Switched Output B
OBattery voltage when active (Max Current: 1 A)
J4-11
Sensor Ground
Provides ground return for 2-wire (isolated) sensors
J4-12
Sensor Input A
High impedance sensor input (0-7,500
Ω)
J4-13
Sensor Input B
Low impedance sensor input (0-750
Ω)
J4-14
Sensor Input C
Universal sensor input (0-750
Ω, 0-7,500 Ω, 0-5 VDC, 4-20mA). See
section for more information.
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...