When entering the Week Scheduler menu, there will be 16 sub menu items, each corresponding to one of the 16
weekly exercise times. If disabled, the entry will have dashed lines, as shown here:
“-------”. If enabled, the day of
week, start time, and duration will be displayed for the menu. Pressing Enter will enter the sub menu for that
exerciser time.
It is recommended that the RapidCore Configurator Software be used to enter the times as this provides a much
more convenient interface, especially if daily exercise times are wanted.
5.6.2.3
Long Time Run
The Long Time Run counter can be used to shut down the controller after a very long period of time. This is
useful for remote primary power applications where the user wants to divide run time between two generators.
When the countdown expires, the controller will shut down. Long Time Run is only active if the generator was
started manually (i.e., by pressing the front RUN button).
Timers > Long Time Run
Name
Range
Default
Description
Start Trigger
Disable
Manual Start
Disable
Set to
“Manual Start” to enable the Long
Time Run feature.
Run Duration
1 ~ 5000 hr
in 1 hr increments
1 hr
The amount of time to run before shutting
down.
5.6.3 Maintenance
The controller has the ability to count down the time between scheduled maintenance events. Once maintenance
is required, the controller will alert the operator via the LCD screen and a switched output (if enabled) wired to a
lamp / horn / buzzer. The following settings are used to configure the maintenance timer.
Timers > Maintenance
Name
Range
Default
Description
Reset Counter
Yes or No
-----
Once the maintenance count interval
expires, use this to reset the time and turn
off the switched output (if enabled). Select
Yes to reset the counter and exit the menu.
Select No to exit the menu without
resetting the counter.
Enable Counter
Enable
Disable
Disable
Enables or disables the maintenance
function.
Count Interval
10 ~ 9990 hr
in 5 hr increments
1000 hr
Determines the number of hours between
required maintenance. A switched output
can be configured to turn on once the
count interval expires.
To determine the amount of time until the next scheduled maintenance, follow these menu steps:
Main Menu > Device Info. > Maintenance
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...